Translations:Charge controller programming/8/en

From Open Source Solar Project
Jump to navigation Jump to search
Example 1: A 48V system has 2 parallel strings of batteries rated at 205Ah @ C/20 rate. The recommended charge rate for this type of battery is 12% of the C/20 rate. What is the maximum charge rate for this battery bank?
Maximum charge rate = C/20 rate × parallel strings × manufacturer maximum C/20 rate percentage
Maximum charge rate = 205Ah x 2 parallel strings x .12 (12%) = 49.2A