Disconnect
A disconnect enables a circuit to be disconnected or isolated from the rest of an electrical system. Disconnects are vital for safety and security as they allow different components in the system to be isolated in order to perform maintenance or service. Traditional disconnects, like in the image, come in countless different sizes and configurations, including custom-built configurations. Although they are not often used in small-scale off-grid installations as most disconnecting needs can be met with breakers, fuse holders, or module connectors which are cheaper and simpler. A traditional disconnect must be rated for the proper current (AC or DC), maximum voltage and maximum current of the circuit. Disconnects can also be found that incorporate fuses for suitable applications.
The appropriate type of disconnect for a circuit depends upon the type of circuit - there are two different types of disconnects that are required in an off-grid PV system.
Contents
Disconnects in a stand-alone PV system
Each off-grid PV system will vary in terms of the necessary disconnect needs both due to design and local requirements. The diagram at right depicts a hypothetical stand-alone system with DC lighting and an inverter for loads. It depicts disconnects that are commonly required in an off-grid system, but simpler systems will not require as many and more complex systems may require additional disconnects.
Power source disconnects
Power source disconnects enable the isolation of any potential power source, including while under load (while current is flowing) in case of emergency. In an off-grid PV system there are three power sources that meet this requirement:
- The PV source (disconnect #2 in the diagram).
- The energy storage system (disconnect #4 in the diagram).
- The inverter (disconnect #5 in the diagram).
If a system incorporates a generator then it will also require a separate disconnect. For off-grid PV systems, breakers are typically used as power source disconnects as they can fulfill the role of an OCPD at the same time, although a properly sized (suitable for DC, correct voltage, correct current) traditional disconnect would work just fine. Any power source disconnect must be rated to disconnect a circuit with current flowing, therefore fuse holders or any type of connector cannot qualify as a power source disconnect as they cannot be opened under load.
Equipment disconnects
All major components in a PV system that may require service or maintenance should have a disconnect that enables them to be isolated from these two potential power sources or any others, although for equipment that is not a power source, it is not necessary that an equipment disconnect be able to function under load. In a typical stand-alone system, there are three pieces of equipment that meet this requirement:
- PV module equipment (disconnect #1 in the diagram).
- Charge controller equipment (disconnect #3 in the diagram).
- Inverter equipment (disconnect #5 in the diagram).
Therefore, touch safe fuse holders and equipment connectors - like MC4 connectors on PV modules - can qualify as equipment disconnects. To be able to use equipment disconnects that are not designed to function under load, it is necessary to have a power source disconnect that can be used to stop any current from flowing before use.