  • Check battery bank voltage. It is a 24V system, therefore it should be above 23V if the system is functioning properly. Measured voltage is 25V. A low voltage battery bank is not likely to be the issue. This also means that the PV source and charge controller are likely functioning properly. The problem likely is with the inverter or circuits connected to the inverter.