h English (en) | The two most common standards for conductor size are American Wire Gauge (AWG) and mm². These two systems are not directly equivalent. The table below shows conductor sizes in AWG and mm² with the ampacity (maximum current) rating of depending upon its temperature rating of the conductor in °C. This chart assumes that there are are 1-3 copper conductors in conduit with a 30°C ambient temperature.<ref name="NEC3"> NFPA 70 - National Electrical Code 2020: Table 310.15(B)(16)</ref> These values must be adjusted for the actual conditions of use of the conductor. |
h Spanish (es) | Los dos estándares más comunes para el tamaño del conductor son American Wire Gauge (AWG) y mm². Estos dos sistemas no son directamente equivalentes. La siguiente tabla muestra los tamaños de los conductores en AWG y mm² con la clasificación de ampacidad (corriente máxima) dependiendo de la clasificación de temperatura del conductor en °C. Esta tabla asume que hay 1-3 conductores de cobre en un conducto con una temperatura ambiente de 30°C. <Ref name = "NEC3"> NFPA 70 - Código Eléctrico Nacional 2020: Tabla 310.15 (B) (16) </ref> Estos valores deben ajustarse a las condiciones reales de uso del conductor. |