Detailed AC/DC system design
Location: Puerto Arturo, Madre de Dios, Peru
GPS coordinates: -12.48694444, -69.21305556
Altitude: 3378m
Description:
A community building with lighting and AC power needs. The system is used all year long, but it is typically only used three to four times a week by community members for meetings, parties, or training sessions. Load usage is typically during the day. The community does not intend on adding any major appliances in the near future.
The system will use DC for lighting and AC for powering loads. DC is used for lighting so that the system continually provides light regardless of whether the inverter is turned on. As the building is used intermittently, the inverter can be turned off to reduce wear and to lessen the liklihood of an accident or damage from lightning.
The system has a system voltage of 24 V, so it will require a DC-DC converter in order to be able to provide 12 V for lighting circuits.
Contents
- 1 Load evaluation
- 2 Weather and solar resource evaluation
- 3 Load and solar resource comparison
- 4 Design parameters
- 5 Energy storage sizing and selection
- 6 Minimum PV source size
- 7 PWM charge controller sizing and selection
- 7.1 Step 1: Determine PV module power rating
- 7.2 Step 2: Determine proposed module configuration
- 7.3 Step 3: Verify excess production
- 7.4 Step 4: Verify charging current
- 7.5 Step 5: Determine final number of PV modules
- 7.6 Step 6: Total PV source current
- 7.7 Step 7: Select a charge controller
- 7.8 Step 8: Determine final PV source power rating
- 8 DC-DC converter sizing and selection
- 9 Inverter sizing and selection
- 10 Wire, overcurrent protection, and disconnect sizing and selection
Load evaluation
Although the system is used only one day a week, inputting 1 day a week of usage for the loads will lead to an undersized array and a poor system design. We will input 4 days a week to ensure that the PV source is still of a reasonable size.
DC load evaluation
Step 1: Fill out DC load chart
April - September | October - March | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
# | Load | Quantity | Watts | Total watts | Duty cycle | Hours per day | Days per week | Average daily DC watt-hours | Hours per day | Days per week | Average daily DC watt-hours |
1 | LED light | 8 | 5 W | 40 W | 1 | 3 hours | 4 days | 69 Wh | 3 hours | 4 days | 69 Wh |
2 | Inverter | 1 | 7 W | 7 W | 1 | 3 hours | 4 days | 12 Wh | 5 hours | 4 days | 12 Wh |
- Load: The make and model or type of load.
- Quantity: The number of the particular load.
- Watts: The power rating in watts of the load.
- Total watts = Quantity × Watts
- Duty cycle = Rated or estimated duty cycle for the load. If the load has no duty cycle a value of 1 should be used. A load with a duty cycle of 20% would be inputted as .2
- Hours per day: The maximum number of hours the load(s) will be operated per day. If the load has a duty cycle 24 hours should be used.
- Days per week: The maximum number of days the load(s) will be operated per week.
- Average daily DC watt-hours = Total watts × Duty cycle × Hours per day × Days per week ÷ 7 days
Step 2: Determine DC energy demand
Total average daily DC watt-hours (April - September) | = sum of Average daily DC watt-hours for all loads for April - September |
---|---|
= 81 Wh |
Total average daily DC watt-hours (October - March) | = sum of Average daily DC watt-hours for all loads for October - March |
---|---|
= 81 Wh |
AC load evaluation
Step 1: Determine inverter efficiency
A conservative inverter efficiency value of .85 is going to be used.
Inverter efficiency | .85 |
---|
Step 2: Fill out AC load chart
April - October | March - September | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
# | Load | Quantity | Watts | Total watts | Duty cycle | Surge factor | Surge watts | Power factor | Volt-amperes (VA) | Hours per day | Days per week | Average daily AC watt-hours | Hours per day | Days per week | Average daily AC watt-hours |
1 | Projector | 1 | 300 W | 300 W | 1 | 0 | 0 | .9 | 333 VA | 3 hours | 4 days | 605 Wh | 3 hours | 4 days | 605 Wh |
2 | Stereo | 1 | 30 W | 30 W | 1 | 0 | 0 | .9 | 33 VA | 3 hours | 4 days | 61 Wh | 3 hours | 4 days | 61 Wh |
3 | Cell phone | 5 | 5 W | 25 W | 1 | 0 | 0 | .9 | 28 VA | 1 hour | 4 days | 17 Wh | 1 hour | 4 days | 17 Wh |
- Load: The make and model or type of load.
- Quantity: The number of the particular load.
- Watts: The power rating in watts for the load.
- Total watts = Quantity × Watts
- Duty cycle = Rated or estimated duty cycle for the load. If the load has no duty cycle a value of 1 should be used. A load with a duty cycle of 20% would be inputted as .2
- Surge factor = Rated or estimated duty cycle for the load. Common values are between 3-5. If the load does not have a surge requirement a value of 0 should be used.
- Power factor = Rated or estimated power factor for the load.
- Volt-amperes (VA) = Total watts ÷ Power factor
- Hours per day: The maximum number of hours the load(s) will be operated per day. If the load has a duty cycle 24 hours should be used.
- Days per week: The maximum number of days the load(s) will be operated per week.
- Average daily AC Watt-hours = Total watts × Duty cycle ÷ Inverter efficiency (Step 1) × Hours per day × Days per week ÷ 7 days
Step 3: Deteremine AC energy demand
Total average daily AC watt-hours (April - September) | = sum of Average daily AC watt-hours for all loads for April - September |
---|---|
682 Wh |
Total average daily AC watt-hours (October - March) | = sum of Average daily AC watt-hours for all loads for October - March |
---|---|
682 Wh |
Step 4: Determine AC power demand
Total VA | = sum of volt-amperes (VA) |
---|---|
394 VA |
Total VA with surge watts | = sum of Surge watts for all loads + Total VA |
---|---|
394 VA |
Total average daily energy demand
The total energy demand for the system is the added Average daily DC-watt hours and Average daily AC watt-hours for each time period.
Average daily watt-hours required (April - September) | = Total average daily DC watt-hours (April - October) + Total average daily AC watt-hours (April - September) |
---|---|
= 81 Wh + 682 Wh = 763 Wh |
Average daily watt-hours required (April - September) | = Total average daily DC watt-hours (October - March) + Total average daily AC watt-hours (October - March) |
---|---|
= 81 Wh + 682 Wh = 763 Wh |
Weather and solar resource evaluation
Maximum ambient temperature = 35°C
Minimum ambient temperature = 15°C
Maximum indoor temperature = 30°C
Minimum indoor temperature = 20°C
Load and solar resource comparison
Step 1: Determine monthly ratio of energy demand to solar resource
Month | Average monthly insolation | Total average daily energy demand | Ratio |
---|---|---|---|
January | 131.2 kWh/m² | 763 Wh | 5.81 |
February | 110.5 kWh/m² | 763 Wh | 6.90 |
March | 145.2 kWh/m² | 763 Wh | 5.25 |
April | 143.5 kWh/m² | 763 Wh | 5.32 |
May | 123.2 kWh/m² | 763 Wh | 6.19 |
June | 132.8 kWh/m² | 763 Wh | 5.75 |
July | 143.3 kWh/m² | 763 Wh | 5.32 |
August | 167.6 kWh/m² | 763 Wh | 4.55 |
September | 112.4 kWh/m² | 763 Wh | 6.79 |
October | 147.0 kWh/m² | 763 Wh | 5.19 |
November | 139.0 kWh/m² | 763 Wh | 5.49 |
December | 134.3 kWh/m² | 763 Wh | 5.68 |
- Month: The month of the year.
- Average monthly insolation: Solar resource data obtained for the location from Weather and solar resource evaluation.
- Total average daily energy demand for the month from the load evaluation.
- Ratio = Total average daily energy demand ÷ Average monthly insolation
Step 2: Determine design values
Design daily insolation | = Average monthly insolation from month with the highest ratio ÷ 30 |
---|---|
= 110.5 kWh/m² ÷ 30 = 3.7 kWh/m² |
Design daily watt-hours required | = Total average daily energy demand from month with the highest ratio |
---|---|
= 763 Wh |
Design parameters
System voltage parameter = 24 V
- This system will be built with a 24 volt nominal voltage in order to be able to use a 72-cell module. It could also easily be built as a 12 volt system.
Irradiance safety parameter = 1.25
- The irradiance safety parameter is always the same.
Continuous duty safety parameter = 1.25
- The continuous duty safety parameter is always the same.
Low voltage disconnect parameter = 22.2 V
- A simple charge controller with a pre-programmed low voltage disconnect will be used.
Energy storage sizing and selection
Step 1: Determine depth of discharge parameter
For this project a depth of discharge of .5 (50%) is a good compromise.
- Depth of discharge = .5
Step 2: Determine days of autonomy parameter
The building is used intermittently, but as the building serves an important need for the community it should still have at least 2 days of autonomy. The energy storage system size has already been reduced as all loads in the load evaluation were put in as only being used 4 days per week, but this calculation only works if the usage is spread out throughout the week. In this case, all of the usage will occurr during one day.
- Days of autonomy = 2
Step 3: Determine battery temperature correction factor
The minimum indoor temperature was determined to be 20°C. An AGM battery will be used to avoid regular maintenance.
- Battery temperature correction factor = 1.03
Correction factors for various battery types:[1]
Temperature | FLA | AGM | Gel |
---|---|---|---|
25°C | 1.00 | 1.00 | 1.00 |
20°C | 1.06 | 1.03 | 1.04 |
15°C | 1.13 | 1.05 | 1.07 |
10°C | 1.19 | 1.08 | 1.11 |
5°C | 1.29 | 1.14 | 1.18 |
0°C | 1.39 | 1.20 | 1.25 |
-5°C | 1.55 | 1.28 | 1.34 |
-10°C | 1.70 | 1.35 | 1.42 |
Step 4: Calculate total Ah required
Total Ah required | = Average daily Watt-hours required ÷ System voltage parameter × Battery temperature correction factor (Step 3) × Days of autonomy parameter (Step 2) ÷ Depth of discharge parameter (Step 1) |
---|---|
= 763 Wh ÷ 24 V × 1.03 × 2 days ÷ .5 = 131 Ah |
Step 5: Calculate number of batteries in series
A 12 V battery is ideal for a system of this size.
Batteries in series | = System voltage parameter ÷ Chosen battery voltage |
---|---|
= 24 V ÷ 12 V | |
= 2 × 12 V battery |
Step 6: Calculate number of batteries in parallel
A Trojan 12 V 135 Ah AGM battery will be used with this design. Specifications sheet
Batteries in parallel | = Total Ah required (step 4) ÷ Chosen battery Ah rating |
---|---|
= 131 Ah ÷135 Ah = .97 | |
= Round up to 1 × 135 Ah battery. |
Step 7: Calculate final Ah capacity
Final Ah capacity | = Number of batteries in parallel (Step 7) × Chosen battery Ah rating |
---|---|
= 2 batteries in parallel × 135 Ah = 135 Ah |
Minimum PV source size
Step 1: Deteremine PV source loss parameters
The PV module(s) will be mounted on a pole mount system.
- Module degradation parameter = .94
- Shading loss parameter = .96
- Soiling loss parameter = .97
- Wiring loss parameter = .96
- Module mismatch parameter = 1
- Mounting system temperature adder = 20°C for a pole mount
- PV source temperature loss parameter = -.41%/°C
PV source temperature loss parameter = 1 + (Maximum ambient temperature + Mounting system temperature adder - 25°C) x Temperature coefficient of max power %/°C ÷ 100 = 1 + (35°C + 20°C - 25°C) x -.41%/°C ÷ 100 = .88
Total PV source loss parameter = Module degradation parameter × Shading loss parameter × Soiling loss parameter × Wiring loss parameter × Module mismatch parameter × PV source temperature loss parameter = .94 × .96 × .97 × .96 × 1 × .88 = .74
Step 2: Charge controller efficiency parameter
All charge controllers lose a certain percentage of all energy that is produced as heat as it is transferred to the energy storage system and loads. For both PWM and MPPT charge controllers a value of .98 (98% efficient) can be used.
Step 3: Energy storage efficiency parameter
The system will use an AGM battery, which is a VRLA battery.
- Valve-regulated lead acid (VRLA) battery efficiency = .85 (85% efficient)
Step 4: Deteremine minimum size of the PV source
Minimum PV source size | = Design daily watt-hours required ÷ Design daily insolation ÷ Total PV source loss parameter (Step 1) ÷ Charge controller efficiency parameter (Step 2) ÷ Energy storage efficiency parameter (Step 3) |
---|---|
= 763 Wh ÷ 3.7 kWh/m² ÷ .74 ÷ .98 ÷ .85 = 335 W |
Step 5: Determine charge controller type
A PWM charge controller is a reliable, low-cost option for a small system like this.
PWM charge controller sizing and selection
Step 1: Determine PV module power rating
The chosen system voltage limits the choices of modules and configurations that are possible with a PWM charge controller. A 24 volt system requires 1 × 72-cell module per string. The minimum PV source size was determined to be 335 W.
A Canadian Solar 340W 72-cell polycrystalline PV module will be used for the design. Specifications sheet
PV module power rating | = 340 W |
---|
Number of modules in series | = 1 module |
---|
Step 2: Determine proposed module configuration
This calculation will give a minimum number of PV modules - the result should always be rounded up. Different modules sizes and configurations can be explored to find the optimal design.
Minimum number of PV modules | = Minimum PV source size ÷ PV module power rating (Step 1) |
---|---|
= 335 W ÷ 340 W = .99 | |
= 1 × 340 W module |
Minimum number of modules in parallel | = Minimum number of PV modules ÷ Number of modules in series (Step 1) |
---|---|
= 1 ÷ 1 = 1 |
Step 3: Verify excess production
This system is not used everyday, therefore it will generate sufficient energy on the days when it is not used to recharge the energy storage system.
Step 4: Verify charging current
This system will use an AGM battery, so that charge current from the PV source should be between .05 (5%) and .2 (20%) of its C/20 rating.
Available charging current | = Maximum power current (Imp) × Minimum number of PV modules in parallel |
---|---|
= 9.05 A × 1 = 9.05 A |
Percentage of C/20 rate | = Available charging current ÷ Final Ah capacity |
---|---|
= 9.05 A ÷ 135 Ah = .07 |
The PV source can supply .07 (7%) of the C/20 current rating of the energy storage system, which is more than .05 (5%) and less than .2 (20%). The PV source configuration is okay.
Step 5: Determine final number of PV modules
Determine a final number of modules and a series/parallel configuration that can meet the requirements of Step 1, Step 2, Step 3, and Step 4.
Final number of PV modules | = 1 |
---|
Final number of PV modules in series | = 1 |
---|
Final number of PV modules in parallel | = 1 |
---|
Step 6: Total PV source current
This calculation will give a minimum current rating to use as a basis for selecting the charge controller. The Isc rating of the PV module can be found on its specifications sheet.
Total PV source current | = Final number of PV modules (Step 5) × Isc rating of chosen module (Step 1) × Irradiance safety parameter |
---|---|
= 1 × 9.62 A × 1.25 = 12 A |
Step 7: Select a charge controller
The final chosen charge controller should:
- Function at the system voltage.
- The charge controller(s) should have a total current rating that is larger than the minimum current rating (Step 6).
A Victron BlueSolar PWM-Pro 12V/24V 20 A charge controller will be used. Specifications sheet
The result of the following equation should always be rounded up.
Number of charge controllers | = Total PV source current (Step 6) ÷ Chosen charge controller current rating |
---|---|
= 12 A ÷ 20 A = .6 = 1 (round up to 1 charge controller) |
Step 8: Determine final PV source power rating
PV source power rating | = PV module power rating (Step 1) × Final number of PV modules in parallel (Step 5) |
---|---|
= 340 W × 1 = 340 W |
DC-DC converter sizing and selection
Minimum current rating of the DC-DC converter | = Sum of all the power rating of all loads/lights ÷ Output voltage |
---|
Inverter sizing and selection
The basic considerations for sizing and selecting an inverter are the following:
- The voltage must match the system voltage.
- The inverter should be able to meet the continuous power demand for all loads that will operate at the same time.
- The inverter should be able to meet the continuous power demand for all loads and the surge power demand for all loads that will operate at the same time.
Step 1: Determine the inverter continuous output rating
Minimum inverter continuous duty rating | = Total VA |
---|---|
394 VA |
Step 2: Determine minimum inverter surge rating
Minimum inverter surge rating | = Total VA with surge watts |
---|---|
394 VA |
Step 3: Determine final inverter continuous duty rating
The chosen inverter should:
- Match the system voltage.
- Have a larger continuous output rating than determined in Step 1.
- Have a larger surge rating than the determined in Step 2.
An Victron Phoenix 500 W, 24 V inverter will be used. Specifications sheet
Step 4: Verify that maximum continuous current of inverter is acceptable
The energy storage system must be large enough to be able to supply the continuous current that the inverter requires. Using an inverter that is oversized relative to the energy storage system can damage the batteries and can cause the system to function improperly. It is recommended that the continous current required by the inverter not exceed .13 (13%) of the Final Ah capacity of the energy storage system for lead acid batteries and .2 (20%) for AGM batteries. If this value is exceeded, then the size of the energy storage system should be increased.
Maximum recommended discharge current | = Final Ah capacity × (.13 for FLA and gel batteries, .2 for AGM batteries) |
---|---|
= 135 Ah × .2 = 27 A |
Inverter continuous duty input current | = Final inverter continuous duty rating (Step 3) ÷ System voltage parameter ÷ Inverter efficiency parameter |
---|---|
= 800 W ÷ 24 V ÷ .85 = 24.5 A |
The inverter at maximum capacity will draw less than .2 (20%) of the C/20 rate of the energy storage system. The inverter size is okay.
Wire, overcurrent protection, and disconnect sizing and selection
The chosen wire for a circuit must meet the requirements set out in each phase of this process. The wire size must be increased if it fails to meet any of these phases and then the process must be performed again with the new wire size.
PV source circuit
Phase 1: Maximum circuit current
Maximum circuit current | = PV module Isc × Irradiance safety parameter |
---|---|
= 9.62 A × 1.25 = 12.03 A |
Phase 2: Wire ampacity
There will only be two current-carrying conductors in the conduit. The maximum ambient temperature 35°C. 90°C rated PV wire will be used for this circuit.
The minimum wire size for a circuit can be using the following steps:
- Determine the ambient temperature correction factor based upon the maximum ambient temperature using the ambient temperature correction factor table. The ambient temperature correction factor for this circuit is .96 because it is a 90°C rated wire with a maximum ambient temperature of 35°C.
- Determine the conduit fill correction factor based upon the number of number of conductors in the conduit using the conduit fill correction factor table There will only be two current-carrying conductors in the conduit, so the conduit correction fill factor is 1.
- Determine the total wire correction parameter based upon the smaller of: the Ambient temperature correction multiplied by the Conduit fill correction factor or .8 (a safety factor from the US National Electrical code).
- Determine minimum wire ampacity. Divide the maximum circuit current (Phase 1) by the total wire correction factor (Step 3)
- Select a wire size with a maximum rated ampacity equal to or above the minimum wire ampacity calculated in the previous step using the allowable wire ampacity table. A 4 mm² PV wire with an ampacity rating of 30 A at 90°C will be used for this circuit as this is a commonly used wire type and size for a circuit of this type. 30 A is larger than the required 15.04 A ampacity.
Total wire correction parameter | = Smaller of (Ambient temperature correction factor × Conduit fill correction factor) or .8 |
---|---|
= Smaller of (.96 × 1) or .8 = .8 |
Minimum wire ampacity | = Maximum circuit current (Phase 1) ÷ Total wire correction parameter (Step 3) |
---|---|
= 12.03 A ÷ .8 = 15.04 A |
Phase 3: Overcurrent protection and disconnects
This circuit, since it only has 1 PV module, does not require an OCPD, but one will be located near the PV equipment to provide a PV power source disconnect.
The appropriate overcurrent protection device size can be determined by:
- Determine the minimum size
- A standard 16 A DC breaker will be used. This is breaker is larger than the required minimum OCPD size, but smaller than the rated 30 A ampacity of the wire that it will protect.
- Verify that the chosen OCPD size from Step 2 will protect the wire size chosen in Phase 2 from excessive current under the conditions of use. The current rating of the chosen breaker size (Step 2) must be less than the calculated maximum current under conditions of use unless the calculated maximum current under conditions of use is between standard OCPD values, in this case the next largest breaker can be chosen.
Maximum current under conditions of use = Wire ampacity from allowable wire ampacity table × Total wire correction parameter (Phase 2). = 30 A × .8 = 24 A Verify OCPD under conditions of use = Maximum current under conditions of use must be greater than the current rating of the chosen OCPD (Step 2) = 24 A is greater than 16 A.
Minimum OCPD size | = Maximum circuit current (Phase 1) × 1.25 |
---|---|
= 12.03 A × 1.25 = 15.04 A |
The OCPD size is okay.
Phase 4: Voltage drop
If the voltage drop for the wire chosen in Phase 2 for a particular circuit is not within the recommended values, then using a larger sized wire should be considered. Increasing the wire size will not affect any other part of this process; the calculated OCPD size can remain the same.
This circuit will be 6 meters long one-way. It is 4 mm² wire with a resistance value in (Ω/Km) of 6.73 Ω. It is recommended that the voltage drop between the PV source and the charge controller be kept below 2%. The circuit current is the Imp of the PV module: 4.44 A. The nominal circuit voltage is the Vmp of the PV module: 18 V.
Voltage drop | = 2 x Circuit current x One-way circuit length (m) x Resistance (Ω/Km) ÷ 1000 |
---|---|
= 2 × 9.02 A × 6m × 6.73 Ω ÷ 1000 = .73 V |
Percentage voltage drop | = Voltage drop ÷ Nominal circuit voltage x 100 |
---|---|
= .73 V ÷ 36 V × 100 = 2% |
2% voltage drop for this circuit is acceptable. The wire size is okay.
Phase 5: Terminal temperature ratings
The PV wire is rated at 90°C, but the terminals on the charge controller and breaker are rated at 75°C. It must be verified that the OCPD will still protect these terminals at their lower temperature rating. If the wire is not protected by the OCPD at the temperature rating of the terminals in the circuit, then the wire size must be increased until the circuit passes this test. No other calculations need to be performed again. Increasing the wire size will have the added benefit of decreasing voltage drop.
Step 1: Maximum ampacity based upon terminal temperature rating
Maximum ampacity based upon terminal temperature rating | = Wire size (Phase 2) ampacity at terminal temperature rating from allowable wire ampacity table × Total wire correction parameter (Phase 2) |
---|---|
= 25 A × .8 = 20 A |
Step 2: Verify OCPD protection of terminals
Verify OCPD protection of terminals | = Maximum current considering terminal temperature rating (Step 1) must be greater than the current rating of the chosen OCPD (Phase 3) |
---|---|
= 20 A is greater than the the 16 A current rating of the breaker |
Wire and OCPD size are okay.
Charge controller output circuit
This same size wire will be used from the charge controller to the battery with one overcurrent protection device which will also serve as a power source disconnect.
Phase 1: Maximum circuit current
Maximum circuit current | = Current rating of the charge controller |
---|---|
= 20 A |
Phase 2: Wire ampacity
There will only be two current-carrying conductors in the conduit. The maximum indoor temperature 30°C. 90°C dry/wet rated wire will be used for this circuit.
The minimum wire size for a circuit can be using the following steps:
- Determine the ambient temperature correction factor based upon the maximum ambient temperature using the ambient temperature correction factor table. The ambient temperature correction factor for this circuit is 1.00 because it is a 90°C rated wire with a maximum indoor temperature of 30°C.
- Determine the conduit fill correction factor based upon the number of number of conductors in the conduit using the conduit fill correction factor table There will only be two current-carrying conductors in the conduit, so the conduit correction fill factor is 1.
- Determine the total wire correction parameter based upon the smaller of: the Ambient temperature correction multiplied by the Conduit fill correction factor or .8 (a safety factor from the US National Electrical code).
- Determine minimum wire ampacity. Divide the maximum circuit current (Phase 1) by the total wire correction factor (Step 3)
- Select a wire size with a maximum rated ampacity equal to or above the minimum wire ampacity calculated in the previous step using the allowable wire ampacity table. A 6 mm² 90°C dry/wet rated wire with an ampacity rating of 40 A at 90°C will be used for this circuit as this is a commonly used wire type and size for a circuit of this type. 40 A is larger than the required 25 A ampacity.
Total wire correction parameter | = Smaller of (Ambient temperature correction factor × Conduit fill correction factor) or .8 |
---|---|
= Smaller of (1.00 × 1) or .8 = .8 |
Minimum wire ampacity | = Maximum circuit current (Phase 1) ÷ Total wire correction parameter (Step 3) |
---|---|
= 20 A ÷ .8 = 25 A |
Phase 3: Overcurrent protection and disconnects
This circuit will use an OCPD to protect it from excessive currents from the energy storage system and as an equipment disconnect, so that it can be disconnected from the energy storage system as needed.
The appropriate overcurrent protection device size can be determined by:
- Determine the minimum size
- A standard 25 A DC breaker will be used. This is breaker is larger than the required minimum OCPD size, but smaller than the 30 A rated ampacity of the wire that it will protect.
- Verify that the chosen OCPD size from Step 2 will protect the wire size chosen in Phase 2 from excessive current under the conditions of use. The current rating of the chosen breaker size (Step 2) must be less than the calculated maximum current under conditions of use unless the calculated maximum current under conditions of use is between standard OCPD values, in this case the next largest breaker can be chosen.
Maximum current under conditions of use = Wire ampacity from allowable wire ampacity table × Total wire correction parameter (Phase 2). = 35 A × .8 = 28 A Verify OCPD under conditions of use = Maximum current under conditions of use must be greater than the current rating of the chosen OCPD (Step 2) = 28 A is greater than 25 A.
Minimum OCPD size | = Maximum circuit current (Phase 1) × 1.25 |
---|---|
= 20 A × 1.25 = 25 A |
The OCPD size is okay.
Phase 4: Voltage drop
If the voltage drop for the wire chosen in Phase 2 for a particular circuit is not within the recommended values, then using a larger sized wire should be considered. Increasing the wire size will not affect any other part of this process; the calculated OCPD size can remain the same.
This circuit will be .5 meters long one-way as it only needs to reach the DC busbars where the battery circuit is connected. It is 6 mm² wire with a resistance value in (Ω/Km) of 4.226 Ω. It is recommended that the voltage drop between the charge controller and energy storage system be less than 1.5%. The circuit current is the Imp of the PV module: 9.02 A. The nominal circuit voltage is the system voltage: 24 V.
Voltage drop | = 2 x Circuit current x One-way circuit length (m) x Resistance (Ω/Km) ÷ 1000 |
---|---|
= 2 × 9.06 A × .5m × 4.226 Ω ÷ 1000 = .04 V |
Percentage voltage drop | = Voltage drop ÷ Nominal circuit voltage voltage x 100 |
---|---|
= .04 V ÷ 24 V × 100 = .17% |
.17% voltage drop for this circuit is acceptable. The wire size is okay.
Phase 5: Terminal temperature ratings
The wire is rated at 90°C, but the terminals on the charge controller and breaker are rated at 75°C. It must be verified that the OCPD will still protect these terminals at their lower temperature rating. If the wire is not protected by the OCPD at the temperature rating of the terminals in the circuit, then the wire size must be increased until the circuit passes this test. No other calculations need to be performed again. Increasing the wire size will have the added benefit of decreasing voltage drop.
Step 1: Maximum ampacity based upon terminal temperature rating
Maximum ampacity based upon terminal temperature rating | = Wire size (Phase 2) ampacity at terminal temperature rating from allowable wire ampacity table × Total wire correction parameter (Phase 2) |
---|---|
= 35 A × .8 = 28 A |
Step 2: Verify OCPD protection of terminals
Verify OCPD protection of terminals | = Maximum current considering terminal temperature rating (Step 1) must be greater than the current rating of the chosen OCPD (Phase 3) |
---|---|
= 28 A is greater than the the 25 A current rating of the breaker |
Wire and OCPD size are okay.
Charge controller load circuit
Phase 1: Maximum circuit current
Maximum circuit current | = Current rating of the charge controller lighting/load circuit |
---|---|
= 20 A |
Phase 2: Wire ampacity
There will only be two current-carrying conductors in the conduit. The maximum indoor temperature 20°C. 90°C dry/wet rated wire will be used for this circuit.
The minimum wire size for a circuit can be using the following steps:
- Determine the ambient temperature correction factor based upon the maximum ambient temperature using the ambient temperature correction factor table. The ambient temperature correction factor for this circuit is 1.00 because it is a 90°C rated wire with a maximum indoor temperature of 30°C.
- Determine the conduit fill correction factor based upon the number of number of conductors in the conduit using the conduit fill correction factor table There will only be two current-carrying conductors in the conduit, so the conduit correction fill factor is 1.
- Determine the total wire correction parameter based upon the smaller of: the Ambient temperature correction multiplied by the Conduit fill correction factor or .8 (a safety factor from the US National Electrical code).
- Determine minimum wire ampacity. Divide the maximum circuit current (Phase 1) by the total wire correction factor (Step 3)
- Select a wire size with a maximum rated ampacity equal to or above the minimum wire ampacity calculated in the previous step using the allowable wire ampacity table. A 6 mm² 90°C dry/wet rated wire with an ampacity rating of 40 A at 90°C will be used for this circuit as this is a commonly used wire type and size for a circuit of this type. 40 A is larger than the required 12.5 A ampacity.
Total wire correction parameter | = Smaller of (Ambient temperature correction factor × Conduit fill correction factor) or .8 |
---|---|
= Smaller of (1.00 × 1) or .8 = .8 |
Minimum wire ampacity | = Maximum circuit current (Phase 1) ÷ Total wire correction parameter (Step 3) |
---|---|
= 10 A ÷ .8 = 12.5 A |
Phase 3: Overcurrent protection and disconnects
This circuit does not require an OCPD if the available current is limited by another OCPD or the charge controller - in this case there is both a 25 A OCPD on the connection to the battery and the charge controller itself is current limited to 20 A. It is necessary to check to make sure that the terminals and wire will be protected by the other OCPD under the conditions of use - the calculation from Phase 5 can be used here.
Step 1: Maximum ampacity based upon terminal temperature rating
Maximum ampacity based on terminal temperature rating | = Wire size (Phase 2) ampacity at terminal temperature rating from allowable wire ampacity table × Total wire correction parameter (Phase 2) |
---|---|
= 35 A × .8 = 28 A |
Step 2: Verify OCPD protection of terminals
Verify OCPD protection of terminals | = Maximum current considering terminal temperature rating (Step 1) must be greater than the current rating of the chosen OCPD (Phase 3 or the maximum charge controller output) |
---|---|
= 28 A is greater than the the 25 A current rating of the breaker on the charge controller output circuit and the 20 A rating of the charge controller load circuit |
No OCPD required
Phase 4: Voltage drop
If the voltage drop for the wire chosen in Phase 2 for a particular circuit is not within the recommended values, then using a larger sized wire should be considered. Increasing the wire size will not affect any other part of this process; the calculated OCPD size can remain the same.
This circuit will be .25 meters long one-way. It is 6 mm² wire with a resistance value in (Ω/Km) of 4.226 Ω. It is recommended that the voltage drop between the charge controller and any lights be kept below 5%. The circuit current is the current required by The circuit nominal voltage is the Nominal circuit voltage is the system voltage: 12 V.
Charge controller load circuit current | = Power rating of all DC loads ÷ Nominal circuit voltage |
---|---|
= 40 W ÷ 12 V = 4.67 A |
Voltage drop | = 2 x Circuit current x One-way circuit length (m) x Resistance (Ω/Km) ÷ 1000 |
---|---|
= 2 × 4.67 A × .25m × 6.73 Ω ÷ 1000 = .016 V |
Percentage voltage drop | = Voltage drop ÷ Nominal circuit voltage x 100 |
---|---|
= .016 V ÷ 12 V × 100 = .13% |
.13% voltage drop for this circuit is acceptable. The wire size is okay.
Phase 5: Terminal temperature ratings
This check was performed in Phase 3 to verify that no OCPD is required.
Charge controller branch circuit example
All DC branch circuits can be calculated in the same way as this example. This circuit has 3 × 5 W light bulbs.
Phase 1: Maximum circuit current
Maximum circuit current | = Power rating of all DC loads on the circuit ÷ Nominal circuit voltage |
---|---|
= (3 × 5 W) ÷ 12 V = 1.25 A |
Phase 2: Wire ampacity
There will only be two current-carrying conductors in the conduit. The maximum indoor temperature 20°C. 90°C dry/wet rated wire will be used for this circuit.
The minimum wire size for a circuit can be using the following steps:
- Determine the ambient temperature correction factor based upon the maximum ambient temperature using the ambient temperature correction factor table. The ambient temperature correction factor for this circuit is 1.08 because it is a 90°C rated wire with a maximum indoor temperature of 20°C.
- Determine the conduit fill correction factor based upon the number of number of conductors in the conduit using the conduit fill correction factor table There will only be two current-carrying conductors in the conduit, so the conduit correction fill factor is 1.
- Determine the total wire correction parameter based upon the smaller of: the Ambient temperature correction multiplied by the Conduit fill correction factor or .8 (a safety factor from the US National Electrical code).
- Determine minimum wire ampacity. Divide the maximum circuit current (Phase 1) by the total wire correction factor (Step 3)
- Select a wire size with a maximum rated ampacity equal to or above the minimum wire ampacity calculated in the previous step using the allowable wire ampacity table. A 2.5 mm² 90°C dry/wet rated wire with an ampacity rating of 25 A at 90°C will be used for this circuit as this is a commonly used wire type and size for a circuit of this type. 25 A is larger than the required 12.5 A ampacity.
Total wire correction parameter | = Smaller of (Ambient temperature correction factor × Conduit fill correction factor) or .8 |
---|---|
= Smaller of (1.08 × 1) or .8 = .8 |
Minimum wire ampacity | = Maximum circuit current (Phase 1) ÷ Total wire correction parameter (Step 3) |
---|---|
= 1.25 A ÷ .8 = 1.56 A |
Phase 3: Overcurrent protection and disconnects
This circuit does not require an OCPD if the available current is limited by another OCPD or the charge controller - in this case there is both a 13 A OCPD on the connection to the battery and the charge controller itself is current limited to 10 A. It is necessary to check to make sure that the terminals and wire will be protected by the other OCPD under the conditions of use - the calculation from Phase 5 can be used here.
Step 1: Maximum ampacity based upon terminal temperature rating
Maximum ampacity based on terminal temperature rating | = Wire size (Phase 2) ampacity at terminal temperature rating from allowable wire ampacity table × Total wire correction parameter (Phase 2) |
---|---|
= 20 A × .8 = 16 A |
Step 2: Verify OCPD protection of terminals
Verify OCPD protection of terminals | = Maximum current considering terminal temperature rating (Step 1) must be greater than the current rating of the chosen OCPD (Phase 3 or the maximum charge controller output) |
---|---|
= 16 A is greater than the the 13 A current rating of the breaker on the charge controller output circuit and the 10 A rating of the charge controller load circuit |
No OCPD required
Phase 4: Voltage drop
If the voltage drop for the wire chosen in Phase 2 for a particular circuit is not within the recommended values, then using a larger sized wire should be considered. Increasing the wire size will not affect any other part of this process; the calculated OCPD size can remain the same.
This circuit will be 8m meters long one-way. It is 2.5 mm² wire with a resistance value in (Ω/Km) of 10.7 Ω. It is recommended that the voltage drop between the PV source and the charge controller below 1.5%. The circuit current is operating current and voltage of the charge controller output. Current is total current required by all of the loads on the circuit (same as calculated in Phase 1). Operating voltage is nominal voltage of the system: 12 V.
Voltage drop | = 2 x Circuit current x One-way circuit length (m) x Resistance (Ω/Km) ÷ 1000 |
---|---|
= 2 × 1.25 A × 8m × 10.7 Ω ÷ 1000 = .21 V |
Percentage voltage drop | = Voltage drop ÷ Circuit operating voltage x 100 |
---|---|
= .09 V ÷ 12 V × 100 = 1.75% |
1.75% voltage drop for this circuit is acceptable. The combined voltage drop of this circuit and the charge controller load circuit voltage drop is 1.88%, which is less than the recommended maximum of 3%. The wire size is okay.
Phase 5: Terminal temperature ratings
This check was performed in Phase 3 to verify that no OCPD is required.
- ↑ Trojan Battery Company - Battery Sizing Guidelines https://www.trojanbattery.com/pdf/TRJN0168_BattSizeGuideFL.pdf