Revision as of 08:03, 15 February 2021
Un sistema de puesta a tierra crea una conexión de baja resistencia entre el equipo del sistema y / o un conductor del sistema (llamado un conductor puesto a tierra o conductor neutro) a la tierra mediante el uso de un electrodo de de puesta a tierra. Un sistema de puesta a tierra no es necesario para que funcione un sistema eléctrico, los sistemas de distribución eléctrica en algunos países carecen de cualquier tipo de puesta a tierra y otros tienen complejos sistemas de puesta a tierra con dispositivos de medición adicionales para proteger a los usuarios. Es común que pequeños sistemas FV autónomos carezcan de un sistema de puesta a tierra, ya que aumenta significativamente los costos y el tiempo de instalación y es posible que no produzca beneficios significativos. A medida que aumenta el tamaño de un sismta, el voltaje y el costo del sistema, aumentan los beneficios de un sistema de puesta a tierra. El código eléctrico de cada país contiene información sobre los requisitos y el equipo adecuado para el lugar.[1]
Además, es necesario consultar el manual para cualquier controlador de carga o inversor antes de decidirse por un esquema de puesta a tierra, ya que pueden tener diferentes requisitos de puesta a tierra. Hay algunos casos que vale la pena resaltar aquí:
- Hay algunos inversores pequeños - onda sinusoidal modificada y onda cuadrada - que se destruirán si se conectan en un sistema que tiene una puesta a tierra de sistea CA y una puesta a tierra CC, ya que no aíslan correctamente su entrada de CC de la salida de CA.
- Hay algunos controladores de carga que están diseñados para aplicaciones específicas, como instalaciones de telecomunicaciones remotas, que tienen una conexión a tierra positiva.
Contents
Terminología de puesta a tierra
La mayoría de los equipos para sistemas autónomos se pueden utilizar en una variedad de configuraciones de puesta a tierra diferentes; no existe una configuración universal. El enfoque aquí estará en una configuración de puesta a tierra TN-S, que se usa comúnmente para instalaciones FV autónomos. Esta configuración tiene una puesta a tierra de sistema CA con un conductor puesta a tierra (neutro). Hay un conductor puesto a tierra de equipos separada para cada circuito para conectar todas las partes metálicas del sistema que no transportan corriente (gabinetes, cajas de conexiones, componentes principales del sistema, etc).[2] Una configuración de puesta a tierra TN-S tiene dos funciones principales que trabajan juntas:
- Puesta a tierra del sistema: la conexión a tierra del sistema se crea conectando un conductor de corriente de un sistema eléctrico a tierra. Una conexión a tierra adecuada del sistema proporciona un medio para disipar el exceso de electricidad estática creada por la fricción o los rayos. Esto ayuda a garantizar un voltaje estable y protege el equipo del sistema contra daños.
- Puesta a tierra del equipo: la conexión a tierra del equipo se crea conectando a tierra todos los componentes metálicos que no transportan corriente de un sistema. Esto crea una ruta para que cualquier corriente creada por una falla, debido a una falla del aislamiento o una conexión suelta, regrese a través de la conexión a tierra del equipo o la tierra al conductor conectado a tierra.
Un sistema de puesta a tierra adecuado requiere varios componentes diferentes que estén conectados entre sí para que el sistema funcione de manera eficaz y segura.
Componente | Función | - | (1) Electrodo de puesta a tierra | El punto de conexión entre la tierra y el sistema eléctrico. Es importante que un electrodo de puesta a tierra tenga suficiente área de superficie en contacto con la tierra para establecer una buena conexión. Hay muchos tipos diferentes de electrodos de puesta a tierra: varillas de cobre, varillas de acero, placas de cobre, las tuberías metálicas de un edificio o una conexión adecuada a la barra de refuerzo utilizada en los cimientos de una edificio. El electrodo de puesta a tierra apropiado variará según el código eléctrico, el edificio y el tipo de suelo. | - | (2) Conductor de electrodo de puesta a tierra (GEC) | La conexión que va desde el electrodo hasta la ubicación del resto del equipo eléctrico, generalmente un cable que va desde el electrodo de conexión a tierra hasta un embarrado de puesta a tierra en el panel de distribución principal. | - | (3) Conductor de puesta a tierra de equipos (EGC) | La conexión que va desde el embarrado de puesta a tierra en el panel de servicio principal a todos los componentes metálicos que no transportan corriente de un sistema (conducto, carcasa del inversor, carcasa del controlador de carga, gabinetes, etc.). | - | (4) Puesta a tierra del sistema de CC | La conexión entre un conductor portador de corriente CC en un sistema eléctrico y el conductor de electrodo de puesta a tierra - comúnmente realizado a través de un dispositivo de protección de falla a tierra. | - | (5) Puesta a tierra del sistema de CA | La conexión entre un conductor portador de corriente CA en un sistema eléctrico y el conductor del electrodo de puesta a tierra, generalmente se realiza inmediatamente después de la salida del inversor en un embarrado utilizado para el circuito de salida del inversor o en el panel de distribución principal. La conexión se realiza desde el embarrado de puesta a tierra principal al embarrado del conductor puesto a tierra. Hay algunos inversores que vienen con un sistema de tierra interno preestablecido, por ejemplo, cualquiera que viene con un dispositivo de protección de falla a tierra (GFPD) integrado. No se debe crear una segunda conexion a tierra - si hay mas que uno el sistema no funcionará bien. |
---|
Es importante conocer varios términos que se utilizan cuando se habla de sistemas FV autónomos y el concepto de puesta a tierra:
Term | Definition |
---|---|
Non-current carrying conductor | A conductor that is not intended to regularly carry current as a part of the normal functioning of an electrical system. All grounding conductors fit into this category. |
Current carrying conductor | A conductor that is intended to regularly carry current as part of the normal functioning of an electrical system. All circuits related to the power generation, energy storage, and distribution to loads fit into this category. |
Grounded system | A system that has an AC or DC system ground. The system may be a DC grounded system, an AC grounded system, or an AC/DC grounded system. There is at least one grounded current carrying conductor in the system. |
Ungrounded system | A system that does not have any system ground. There is no grounded current carrying conductor in the system. |
Grounded conductor | A current carrying conductor that has a connection established to ground by an AC or DC system ground. |
Ungrounded conductor | A current carrying conductor that does not have a connection established to ground by an AC or DC system ground. |
Ground faults
A ground fault occurs when a current carrying conductor of an electrical system has an insulation failure or comes loose from a connection and makes contact with something that has a connection to ground. Ground faults can be very dangerous because they can lead to electrocutions and fires, therefore it is important to identify them as quickly as possible and disable them. When there is a ground fault, current escapes the wires of a circuit and seeks other paths to be able to complete the circuit. A person who grabs something that has been energized by a fault to ground can become a path to complete the circuit and be electrocuted. In a properly grounded system, the most common ground fault scenario is a ground fault between an ungrounded current-carrying conductor (black wire) and a grounded piece of equipment. A ground fault can occur with a grounded conductor but it will not typically be apparent until there is a second ground fault involving the ungrounded conductor (black wire).
System grounding and equipment grounding work with overcurrent protection devices, ground fault protection devices, residual current devices and inverter electronics to identify faults and disable them as quickly as possible by opening (disconnecting) the circuit. This system functions because a fault to an equipment grounding conductor will create a short circuit if there is low enough resistance, which will activate these devices and cause them to open (disconnect) the circuit.
An AC ground fault involving an ungrounded conductor typically occurs as follows:
- A ground fault occurs between a grounded piece of equipment and an ungrounded conductor (wire).
- The equipment grounding conductor has a connection - due to the system ground - to the grounded conductor. The current follows it because it is a low resistance path to the grounded conductor, which completes the circuit.
- The current reaches the grounded conductor and this effectively creates a short-circuit which causes the inverter to supply large a amount of current to the newly created low-resistasnce circuit.
- This high current flow will be identified by the inverter electronics, residual current device (RCD) or an overcurrent protection device (OCPD) as a fault, which will cause the one of them to trip and open (disconnect) the circuit. A RCD or inverter electronics will react quicker than an OCPD.
These devices only temporarily remove the hazard, thus after a ground fault occurs it is necessary to carefully troubleshoot the system to locate the fault and fix it.
Grounded and ungrounded systems in practice
The current carrying conductors in a circuit will behave differently depending upon whether they are grounded or not. Grounded and ungrounded systems each carry different advantages and disadvantages.
Ungrounded system
An ungrounded conductor in an ungrounded system will only have a voltage relative to the other ungrounded conductors in the system, but will not have a voltage relative to ground. For a ground fault to pass current and trip a overcurrent protection devices or a residual current device, two seperate ground faults will be required. This means that a person could touch the busbar of either conductor independently at be safe as long as there is no fault.
Ungrounded systems do not readily identify single ground faults, which represents a significant safety hazard as a user or technician may not discover that a fault exists until contact is made with a conductor that would have had no voltage to ground had it not been for the fault. They can also create other additional double-fault scenarios that do not exist in grounded systems that require an overcurrent protection device on all positive and negative wires in a circuit to be properly mitigated.
Conductor | Voltage relative to other conductors |
---|---|
Ungrounded conductor 1 | Will have full circuit voltage relative to the other ungrounded conductor. Will have no voltage relative to ground. |
Ungrounded conductor 2 | Will have full circuit voltage relative to the other ungrounded conductor. Will have no voltage relative to ground. |
Grounding conductors | Will have no voltage relative to either ungrounded conductor 1 or ungrounded conductor 2. |
Grounded system
An ungrounded conductor in a grounded system will have a voltage relative to the grounded conductor and the ground. For a #Ground fault to pass current and trip a overcurrent protection devices or a residual current device, only one ground faults - between the ungrounded conductor and the ground - will be required. This means in this system that a person could touch the busbar of either the grounded conductor or ground and be safe as long as there is no fault.
Grounded systems are better at readily identifying single ground faults and making users or technicians aware that there is an issue. They also avoid the double-fault scenarios that can be an issue for ungrounded systems.
Conductor | Voltage relative to other conductors |
---|---|
Ungrounded conductor | Will have full circuit voltage relative to the grounded conductor, ground, and any grounded equipment. |
Grounded conductor | Will have the full circuit voltage relative to the ungrounded conductor. Will have no voltage relative to ground or any grounded equipment. |
Grounding conductors | Will have full circuit voltage relative to the ungrounded conductor. Will have no voltage relative to the grounded conductor. |