'''Example 1:''' A circuit has 3 x 12 AWG THHW wires. Can these wires fit in a 1/2" (21 mm) EMT conduit with 1 x 90° bend?  
 
'''Example 1:''' A circuit has 3 x 12 AWG THHW wires. Can these wires fit in a 1/2" (21 mm) EMT conduit with 1 x 90° bend?  
 
:*Maximum fill of 40% of the space inside the conduit.  
 
:*Maximum fill of 40% of the space inside the conduit.  
:*Cross-sectional area of conduit ): 195 mm²
+
:*Cross-sectional area of conduit: 195 mm²
 
:*Cross-sectional area of 12 AWG THHN wire: 11.68 mm²
 
:*Cross-sectional area of 12 AWG THHN wire: 11.68 mm²

Latest revision as of 11:54, 14 February 2021

Information about message (contribute)
This message has no documentation. If you know where or how this message is used, you can help other translators by adding documentation to this message.
Message definition (Conduit)
'''Example 1:''' A circuit has 3 x 12 AWG THHW wires. Can these wires fit in a 1/2" (21 mm) EMT conduit with 1 x 90° bend? 
:*Maximum fill of 40% of the space inside the conduit. 
:*Cross-sectional area of conduit: 195 mm²
:*Cross-sectional area of 12 AWG THHN wire: 11.68 mm²
Translation'''Example 1:''' A circuit has 3 x 12 AWG THHW wires. Can these wires fit in a 1/2" (21 mm) EMT conduit with 1 x 90° bend? 
:*Maximum fill of 40% of the space inside the conduit. 
:*Cross-sectional area of conduit: 195 mm²
:*Cross-sectional area of 12 AWG THHN wire: 11.68 mm²

Example 1: A circuit has 3 x 12 AWG THHW wires. Can these wires fit in a 1/2" (21 mm) EMT conduit with 1 x 90° bend?

  • Maximum fill of 40% of the space inside the conduit.
  • Cross-sectional area of conduit: 195 mm²
  • Cross-sectional area of 12 AWG THHN wire: 11.68 mm²