Difference between revisions of "Wire terminal/es"
(Created page with "{| class="wikitable" border=1 ! Color ! Tamaño métrico estándar (mm²) ! Tamaño AWG estándar |- |Rojo | .5-1 mm² | 22-16 AWG |- |Azul | 1.5-2.5 mm² | 16-14 AWG |- |Amar...") |
(Created page with "==Terminales para baterías de plomo-ácido inundadas==") |
||
Line 35: | Line 35: | ||
|} | |} | ||
− | == | + | ==Terminales para baterías de plomo-ácido inundadas== |
The gasses released by flooded lead acid batteries can cause corrosion can occur on terminals over time, which will create a high resistance connection that can represent a safety hazard. There are several recommended practices to avoid corrosion and any resulting issues: | The gasses released by flooded lead acid batteries can cause corrosion can occur on terminals over time, which will create a high resistance connection that can represent a safety hazard. There are several recommended practices to avoid corrosion and any resulting issues: |
Revision as of 12:40, 12 February 2021
Los terminales se utilizan para realizar conexiones mecánicas seguras y duraderas en sistemas eléctricos. Los terminales que se prensan (comprimen) mecánicamente con una herramienta son el estándar para las instalaciones FV autónomos. Un terminal debe elegirse correctamente en función de:[1]
- El tamaño del cable que se insertará en él. Los terminales a menudo se marcarán para el tamaño de cable que se utilizará como en el diagrama.
- El tamaño del perno que se utilizará para sujetarlo. Los terminales deben estar marcados por el tamaño del orificio que tienen.
- El trenzado del cable con el que se utilizará. El cable de batería trenzado fino puede requerir terminales más grandes que el tamaño estándar.
Al engarzar el terminal, se debe utilizar el tamaño y tipo de herramienta de engarzado adecuados para garantizar una buena conexión. Si se utiliza una herramienta inadecuada, como un martillo u otro tipo de alicates, es probable que la conexión se pierda y falle con el tiempo.
Terminales aislados
Los terminales aislados para calibres de cable más pequeños se han estandarizado utilizando un esquema de color simple que funciona tanto para AWG como mm² tamaños de cable.[2]
Color | Tamaño métrico estándar (mm²) | Tamaño AWG estándar |
---|---|---|
Rojo | .5-1 mm² | 22-16 AWG |
Azul | 1.5-2.5 mm² | 16-14 AWG |
Amarillo | 4-6 mm² | 12-10 AWG |
Terminales para baterías de plomo-ácido inundadas
The gasses released by flooded lead acid batteries can cause corrosion can occur on terminals over time, which will create a high resistance connection that can represent a safety hazard. There are several recommended practices to avoid corrosion and any resulting issues:
- Terminals should not be bare copper. They should be tinned (silver in color) as the tin does not corrode like copper.
- Terminals should be coated in anti-corrosive grease.
- Terminals should not leave any copper from the wires exposed. Terminals for use with lead acid batteries should have a closed-end rather than an open end that allows one to see the wire that has been inserted. Additionally, where the wire enters the back of the terminal should be coated in heat shrink or electrical tape to prevent the entrance of gasses produced from the batteries.
Notes/references
- ↑ Thomas & Betts Compression Terminal Catalogue http://www.tnb.com/pubint/docs/colorkeyed_spec.pdf
- ↑ PANDUIT terminal size chart http://www.innovative.com.mx/wp-content/uploads/2015/10/Metric-Ring-Terminal-Vinyl-Insulated-Funnel-Entry.png