Difference between revisions of "PWM charge controller sizing and selection"
Line 82: | Line 82: | ||
====Step 5: Determine final number of PV modules==== | ====Step 5: Determine final number of PV modules==== | ||
Determine a final number of modules and a series/parallel configuration that can meet the requirements of Step 1, Step 2, Step 3, and Step 4. | Determine a final number of modules and a series/parallel configuration that can meet the requirements of Step 1, Step 2, Step 3, and Step 4. | ||
+ | |||
+ | {| class="wikitable" border=1 style="width: 80%;" | ||
+ | ! style="width: 20%"|Final number of PV modules | ||
+ | ! style="text-align:left;"| = | ||
+ | |} | ||
+ | |||
+ | {| class="wikitable" border=1 style="width: 80%;" | ||
+ | ! style="width: 20%"|Final number of PV modules in series | ||
+ | ! style="text-align:left;"| = | ||
+ | |} | ||
+ | |||
+ | {| class="wikitable" border=1 style="width: 80%;" | ||
+ | ! style="width: 20%"|Final number of PV modules in parallel | ||
+ | ! style="text-align:left;"| = | ||
+ | |} | ||
+ | |||
====Step 6: Determine minimum current rating of charge controller==== | ====Step 6: Determine minimum current rating of charge controller==== |
Revision as of 08:59, 17 December 2020
A PWM charge controller is rated to operate at a particular system voltage and maximum current. PV modules designed to work at the system voltage must be connected in parallel in order to achieve the minimum PV source size and the charge controller therefore must be sized to handle this amount of current. If the current rating of a PWM charge controller is exceeded, it can be damaged or destroyed.
Contents
- 1 Step 1: Determine PV module power rating
- 2 Step 2: Determine proposed module configuration
- 3 Step 3: Verify excess production
- 4 Step 4: Verify charging current
- 5 Step 5: Determine final number of PV modules
- 6 Step 6: Determine minimum current rating of charge controller
- 7 Step 7: Select a charge controller
- 8 Step 8: Determine final PV source power rating
- 9 Notes/references
Step 1: Determine PV module power rating
The chosen System voltage limits the choices of modules and configurations that are possible with a PWM charge controller.
- 12 volt system = 1 × 36-cell module per string.
- 24 volt system = 1 × 72-cell module per string or 2 x 36-cell modules in series per string.
- 48 volt system = 2 × 72-cell modules in series per string or 4 x 36-cell modules in series per string.
PV module power rating | = |
---|
Number of modules in series | = |
---|
Step 2: Determine proposed module configuration
This calculation will give a minimum number of PV modules. Different modules sizes and configurations can be explored to find the optimal design.
Minimum number of PV modules | = Minimum PV source size ÷ PV module power rating (Step 1) |
---|
- The final number of PV modules should always be larger than this value, thus if the the result of the calculation is a decimal, it should be rounded up.
Minimum number of modules in parallel | = Minimum number of PV modules ÷ Number of modules in series (Step 1) |
---|
Step 3: Verify excess production
During periods of poor weather or low solar resource, an off-grid PV system is designed to discharge the battery to a certain depth of discharge which can leave the energy storage system depleted. It is important that the energy storage system is brought back up to a full state of charge in short period of time or the cycle life of the batteries will be reduced. The PV array therefore must be sized to generate sufficient excess energy, while continuing to meet all of the power needs from the Load evaluation. OSSP recommends that the array be sufficiently sized to reach a full state of charge within a week or that the system incorporate a generator to ensure adequate charging.
Proposed PV source low insolation production | = PV module power rating (Step 1) × Minimum number of PV modules (Step 2) × Total PV source loss parameter × Design insolation × Charge controller efficiency parameter × Energy storage efficiency parameter |
---|
Daily excess production in Ah | = (Proposed PV source low insolation production - Average daily Watt-hours required) ÷ System voltage parameter |
---|
Ah used at full depth of discharge | = Final Ah capacity × Depth of discharge parameter |
---|
Time to reach full state of charge | = Ah used at full depth of discharge ÷ Daily excess production in Ah |
---|
If the time to reach full state of charge is less than 7 days, then the size of the PV source should be increased until it is below 7 days.
Step 4: Verify charging current
Lead acid batteries last longer and perform better when they are regularly recharged with a current in a certain range - typically between .05-.13 (5-13%) of their C/20 rating.[1] If a system uses many loads during the day, this will limit the available charging current for the energy storage system and should be taken into account by increasing the PV source size. The maximum charging current for most lead acid batteries is between .13 (13%) and .2 (20%) of the C/20 rate.[2] Most designs should have a charge rate between 5-10% - closer to 10% if the system is used heavily during the day. It is necessary to consult the manual or manufacturer for recommended maximum and minimum charging currents.
Minimum required charge current | = Final Ah capacity × .05 |
---|
It is necessary to check the minimum required charge current against the available charge current from the proposed PV source power rating.
Available charging current | = Maximum power current (Imp) × Minimum number of PV modules in parallel |
---|
Percentage of C/20 rate | = Available charging current ÷ Final Ah capacity |
---|
If the number of PV modules does not meet the recommendations outlined above, increasing the PV source in size should be considered.
Step 5: Determine final number of PV modules
Determine a final number of modules and a series/parallel configuration that can meet the requirements of Step 1, Step 2, Step 3, and Step 4.
Final number of PV modules | = |
---|
Final number of PV modules in series | = |
---|
Final number of PV modules in parallel | = |
---|
Step 6: Determine minimum current rating of charge controller
This calculation will give a minimum current rating to use as a basis for selecting the charge controller. The Isc rating of the PV module can be found on its specifications sheet.
Minimum current rating of charge controller | = Final number of PV modules (Step 5) × Isc rating of chosen module (Step 1) × Irradiance safety parameter |
---|
Step 7: Select a charge controller
The final chosen charge controller should:
- Function at the system voltage.
- Have a current rating that is larger than the minimum current rating (Step 6).
Step 8: Determine final PV source power rating
The total power rating of the PV source can be calculated by multiplying the power rating of the chosen PV module by the final number of PV modules (Step 5).
PV source power rating | = PV module power rating (Step 1) × Final number of PV modules in parallel (Step 5) |
---|
Notes/references
- ↑ Trojan Battery Company - User's Guide https://www.trojanbattery.com/pdf/TrojanBattery_UsersGuide.pdf
- ↑ Rolls Battery - Battery User Manual https://rollsbattery.com/public/docs/user_manual/Rolls_Battery_Manual.pdf