Difference between revisions of "Overcurrent protection device"

From Open Source Solar Project
Jump to navigation Jump to search
Line 2: Line 2:
 
[[File:Fusebreaker201021.png|thumb|right|'''Overcurrent Protection Device examples:'''<br/> 1. Breaker 2. Fuse]]
 
[[File:Fusebreaker201021.png|thumb|right|'''Overcurrent Protection Device examples:'''<br/> 1. Breaker 2. Fuse]]
 
All components of an electrical system have a maximum amount of current that they are rated to continuous handle, if this rating is exceeded excess heat will be generated which can result in a fire. Overcurrent protection devices (OCPDs) are used to automatically disconnect a circuit if a certain current is reached for a certain period of time. The size of the required overcurrent protection device is determined by the maximum amount of current that a circuit is anticipated to carry and the [[Wire ampacity|ampacity]] of the circuit wiring. The OCPD must be smaller than the rated [[wire ampacity|ampacity]] of the wire. The most common types of overcurrent protection device that are used in electrical systems are fuses and breakers.  
 
All components of an electrical system have a maximum amount of current that they are rated to continuous handle, if this rating is exceeded excess heat will be generated which can result in a fire. Overcurrent protection devices (OCPDs) are used to automatically disconnect a circuit if a certain current is reached for a certain period of time. The size of the required overcurrent protection device is determined by the maximum amount of current that a circuit is anticipated to carry and the [[Wire ampacity|ampacity]] of the circuit wiring. The OCPD must be smaller than the rated [[wire ampacity|ampacity]] of the wire. The most common types of overcurrent protection device that are used in electrical systems are fuses and breakers.  
 +
 +
==OCPDs in a stand-alone system==
 +
Each PV system will vary in terms of its OCPD needs both due to design and local requirements. The diagram at right depicts a hypothetical stand-alone system with DC ligthting and an inverter for loads. It depicts many OCPDs that are commonly incorporated into an off-grid system, but simpler systems will not require as many and more complex systems will likely require additional OCPDs. Many of these OCPDs can also serve as [[Disconnects|power source disconnects]] and [[Disconnects|equipment disconnects]].
 +
#'''PV source circuit OCPD''' - If a PV source has more than 2 parallel modules or strings of modules, then an OCPD should be incorporated for each one before they are connected together in parallel to avoid a [[Electricity and energy#Circuits: making use of electricity|short-circuit]] that sends all of the current of the array through the fault.
 +
#'''PV output circuit OCPD''' - A breaker is typically installed near the charge controller to serve as an easily accessible means to [[Electricity and energy#Circuits: making use of electricity|open (disconnect)]] the PV source from for safe service and maintenance. This requirement could be met by OCPD #1 if the breakers are near the rest of the equipment.
 +
#Charge controller ouput circuit OCPD - The charge controller output circuit must be protected from faults from the [[Energy storage|energy storage system]].
 +
#DC lighting output circuit OCPD - If a DC circuit is connected directly to the battery bank, whether it passes through a [[Low voltage disconnect|low voltage disconnect]] or not, it is very important that it is protected by an OCPD as a battery bank can supply a tremendous amount of current in a short period of time. If the circuit is run through the lighting/load circuit of a charge controller an OCPD may not be required as the circuit will be current limited, but it is still recommended as it may be protect the charge controller from damage in the event of a fault. A breaker is additionally convenient for turning for service and maintenance.
 +
#DC branch circuit OCPD - All circuits that feed DC loads must be protected from faults from the faults from the [[Energy storage|energy storage system]]. OCPD #4 may provide sufficient protection.
 +
#Inverter input circuit OCPD -
 +
#Inverter output circuit OCPD -
 +
#AC branch circuit OCPD -
 +
#Battery circuit OCPD -
  
 
==Characteristics==
 
==Characteristics==

Revision as of 12:44, 27 October 2020

Overcurrent Protection Device examples:
1. Breaker 2. Fuse

All components of an electrical system have a maximum amount of current that they are rated to continuous handle, if this rating is exceeded excess heat will be generated which can result in a fire. Overcurrent protection devices (OCPDs) are used to automatically disconnect a circuit if a certain current is reached for a certain period of time. The size of the required overcurrent protection device is determined by the maximum amount of current that a circuit is anticipated to carry and the ampacity of the circuit wiring. The OCPD must be smaller than the rated ampacity of the wire. The most common types of overcurrent protection device that are used in electrical systems are fuses and breakers.

OCPDs in a stand-alone system

Each PV system will vary in terms of its OCPD needs both due to design and local requirements. The diagram at right depicts a hypothetical stand-alone system with DC ligthting and an inverter for loads. It depicts many OCPDs that are commonly incorporated into an off-grid system, but simpler systems will not require as many and more complex systems will likely require additional OCPDs. Many of these OCPDs can also serve as power source disconnects and equipment disconnects.

  1. PV source circuit OCPD - If a PV source has more than 2 parallel modules or strings of modules, then an OCPD should be incorporated for each one before they are connected together in parallel to avoid a short-circuit that sends all of the current of the array through the fault.
  2. PV output circuit OCPD - A breaker is typically installed near the charge controller to serve as an easily accessible means to open (disconnect) the PV source from for safe service and maintenance. This requirement could be met by OCPD #1 if the breakers are near the rest of the equipment.
  3. Charge controller ouput circuit OCPD - The charge controller output circuit must be protected from faults from the energy storage system.
  4. DC lighting output circuit OCPD - If a DC circuit is connected directly to the battery bank, whether it passes through a low voltage disconnect or not, it is very important that it is protected by an OCPD as a battery bank can supply a tremendous amount of current in a short period of time. If the circuit is run through the lighting/load circuit of a charge controller an OCPD may not be required as the circuit will be current limited, but it is still recommended as it may be protect the charge controller from damage in the event of a fault. A breaker is additionally convenient for turning for service and maintenance.
  5. DC branch circuit OCPD - All circuits that feed DC loads must be protected from faults from the faults from the energy storage system. OCPD #4 may provide sufficient protection.
  6. Inverter input circuit OCPD -
  7. Inverter output circuit OCPD -
  8. AC branch circuit OCPD -
  9. Battery circuit OCPD -

Characteristics

Graph of different trip curves. The graph depicts a breaker with the same current rating, but comes with different trip curves: B (most sensitive), C (less sensitive), D (most sensitive).

There are innumerable different OCPDs in the market with each one designed to fit a specific purpose. Many OCPDs are similar in appearance, therefore it is very important to revise the fine print on the side of any OCPD being considered to make sure that it is appropriate for the conditions of use.

Current type

OCPDs may be designed to work with AC, DC or both types of current. If a breaker is rated for both AC and DC, it is likely that the DC voltage rating will be lower as DC circuits are more difficult to interrupt.

Current rating

OCPDs will be rated for a specific continous current rating.
Standard international OCPD sizes: 1 A, 2 A, 4 A, 6 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A, 80 A, 100 A and 125 A.
Standard US OCPD sizes per US NEC: 15, 20,25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250,300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000,4000 5000, and 6000 amps. Additional standard fuse sizes are 1, 3, 6, 10, and 601 amps.

Current flow

Some circuits in an off-grid PV system carry current in both directions like the energy storage system circuit as it charges and discharges. This can be an issue for certain types of breakers that are not rated for current flow in both directions. If a breaker is marked on the side specifying a direction for current flow - typically with "line" on top and "load" on the bottom, then it should not be used in a circuit that has current flow in both directions.

Trip curve

OCPDs will have a trip curve which specifies how long the device can sustain current above its continuous duty rating. This is desirable because in electrical systems there are often surge loads that require additional current for a very brief period of time when starting. If an OCPD does not have a slight time delay, it will trip every time a surge load is connected. For all typical circuits in an offgrid PV system, an OCPD with a time delay is recommended.

Maximum voltage

AC and DC breakers will be rated for the maximum circuit voltage that they are intended to work with. It can be difficult to find OCPDs rated to work with DC at higher voltages.

Ampere interrupting capacity rating

Ampere interrupting capacity (AIC) rating is the OCPDs ability to withstand current and still open (shut down) a circuit. This rating is typically hundreds of times the current rating of the breaker with a typical 15A household breaker having an AIC rating of 10,0000A. AIC ratings are typically not relevant in the case of offgrid PV systems.

Mounting type

  • There are many different types of fuse holders and corresponding fuses. They must be designed to work together.
  • Breakers will be designed to be mounted in a specific type of distribution panel or on a DIN rail.

Projected life

  • Fuses only work once and need to be replaced after tripping. For offgrid applications breakers are always preferrable for this reason as acquiring replacement fuses in remote locations can be difficult.
  • Breakers can typically withstand a minimum of hundreds of faults. If a breaker fails, it will typically fail open (circuit disconnected).

Maintenance

There is no maintenance to be done in either case, other than to make sure that the connections to the OCPD remain tight over time.

Recyclability

Standard breakers and fuses typically do not contain anything hazardous, but should be recycled as E-waste as traditional waste disposal streams cannot process them.

Notes