A GFPD plays an important role in a PV system with a DC system ground by helping to prevent fires from ground faults that go undetected by [[Special:MyLanguage/Overcurrent protection device|overcurrent protection devices (OCPDs)]]. A ground fault can go undetected because the OCPDs for the PV source are [[Special:MyLanguage/Wire, overcurrent protection, and disconnect sizing and selection#Phase 3: Overcurrent protection and disconnects|sized to the maximum current of the PV source]], which means that OCPDs are often ineffective against DC ground faults occurring at the PV source as it doesn't exceed their current rating. This can lead to a fire because [[Special:MyLanguage/PV module|PV modules]] will continue to provide current as long as there is sunshine and a circuit. The diagram at right shows how a GFPD operates during a ground fault on an ungrounded DC conductor:
+
==Functioning of a GFPD==

Latest revision as of 07:12, 15 February 2021

Information about message (contribute)
This message has no documentation. If you know where or how this message is used, you can help other translators by adding documentation to this message.
Message definition (Ground fault protection device)
==Functioning of a GFPD==
Translation==Functioning of a GFPD==

Functioning of a GFPD