Difference between revisions of "Load and solar resource comparison"

From Open Source Solar Project
Jump to navigation Jump to search
Line 1: Line 1:
 
[[Category:Site evaluation]]
 
[[Category:Site evaluation]]
The design process for an off-grid PV system should use conservative, worst-case values to ensure that the system is capable of meeting the energy needs of users throughout the year. There are many locations that have a significant seasonal variance in [[Weather and solar resource evaluation|solar resource]] due to poor weather or latitude. Many off-grid PV systems will see a significant variance in [[Load evaluation|how loads are used throughout the year]], especially in locations that are only seasonally occupied. These two different factors - load usage vs. solar resource - make it important to determine what month to use in the system design as the worst-case scenario. An analysis of loads and usage could be performed on a monthly basis, but the most drastic shift in usage likely occurs between the major seasons in a given region meaning two to four times per year. Determining the worst-case month can be done using a simple table and a quick calculation. The values and calculation can be performed in Wh or kWh - the ratio is what is important. The two following values used for the design should be chosen from the month with the highest ratio of average daily watt-hours relative to average insolation:
+
The design process for an off-grid PV system should use conservative, worst-case values to ensure that the system is capable of meeting the energy needs of users throughout the year. There are many locations that have a significant seasonal variance in [[Weather and solar resource evaluation|solar resource]] due to poor weather or latitude. Many off-grid PV systems will see a significant variance in [[Load evaluation|how loads are used throughout the year]], especially in locations that are only seasonally occupied. These two different factors - load usage vs. solar resource - make it important to determine what month to use in the system design as the worst-case scenario. An analysis of loads and usage could be performed on a monthly basis, but the most drastic shift in usage likely occurs between the major seasons in a given region meaning two to four times per year. Determining the worst-case month can be done using a simple table and a quick calculation. The values and calculation can be performed in Wh or kWh - the ratio is what is important. The two following values used for the design should be chosen from the month with the highest ratio of average daily watt-hours relative to average monthly insolation:
  
*Design insolation
+
*Design daily insolation
 
*Design daily watt-hours required
 
*Design daily watt-hours required
  
'''Example 1:''' A potential off-grid PV system in Puerto Maldonado, Madre de Dios, Peru in the Amazon rainforest with [[PV module|PV source]] with a tilt of 12 degrees of PV module tilt. Solar resource data shows that despite being relatively near the equator there is significant monthly variation due to seasonal rains.<ref name="pvwatts"> PVWatts Calculator https://pvwatts.nrel.gov/pvwatts.php</ref> The load evaluation shows that loads will be used more frequently during the rainy season, which is common.  
+
'''Example 1:''' A potential off-grid PV system in Puerto Maldonado, Madre de Dios, Peru in the Amazon rainforest with [[PV module|PV source]] with a tilt of 12 degrees of PV module tilt. Solar resource data shows that despite being relatively near the equator there is significant monthly variation due to seasonal rains.<ref name="pvgis"> EU PVGIS https://re.jrc.ec.europa.eu/pvg_tools/en/#MR</ref> The load evaluation shows that loads will be used more frequently during the rainy season, which is common.  
*July (highlighted in red) has the worst ratio of solar resource relative to energy requirement throughout the year. The average insolation value (3.39 kWh/m²) and Average daily Watt-hours required (3000Wh) from this month should be used in the design.
+
*May (highlighted in red) has the worst ratio of solar resource relative to energy requirement throughout the year. The average monthly insolation value (135.47 kWh/m²) and Average daily Watt-hours required (3000Wh) from this month should be used in the design.
  
 
{| class="wikitable" border=1
 
{| class="wikitable" border=1
Line 15: Line 15:
 
|-
 
|-
 
|January
 
|January
|6.06 kWh/m²
+
|147.27 kWh/m²
 
|2000 Wh
 
|2000 Wh
|330
+
|13.58
 
|-
 
|-
 
|February
 
|February
|6.32 kWh/m²
+
|140.08 kWh/m²
 
|2000 Wh
 
|2000 Wh
|316
+
|14.28
 
|-
 
|-
 
|March
 
|March
|6.49 kWh/m²
+
|166.77 kWh/m²
 
|2000 Wh
 
|2000 Wh
|308
+
|11.99
 
|-
 
|-
 
|April
 
|April
|6.42 kWh/m²
+
|161.56 kWh/m²
|2000 Wh
+
|3000 Wh
|311
+
|18.57
|-
+
|- style="background-color:#F08080;"
 
|May
 
|May
|5.00 kWh/m²
+
|135.47 kWh/m²
|2000 Wh
+
|3000 Wh
|600
+
|22.15
 
|-
 
|-
 
|June
 
|June
|3.75 kWh/m²
+
|157.44 kWh/m²
 
|3000 Wh
 
|3000 Wh
|800
+
|19.05
|- style="background-color:#F08080;"
+
|-
 
|July
 
|July
|3.39 kWh/m²
+
|149.74 kWh/m²
 
|3000 Wh
 
|3000 Wh
|885
+
|20.03
 
|-
 
|-
 
|August
 
|August
|3.69 kWh/m²
+
|178.82 kWh/m²
 
|3000 Wh
 
|3000 Wh
|813
+
|16.78
 
|-
 
|-
 
|September
 
|September
|4.21 kWh/m²
+
|172.36 kWh/m²
 
|3000 Wh
 
|3000 Wh
|713
+
|17.41
 
|-
 
|-
 
|October
 
|October
|5.17 kWh/m²
+
|170.63 kWh/m²
|3000 Wh
+
|2000 Wh
|580
+
|11.72
 
|-
 
|-
 
|November
 
|November
|5.27 kWh/m²
+
|161.02 kWh/m²
 
|2000 Wh
 
|2000 Wh
|380
+
|12.42
 
|-
 
|-
 
|December
 
|December
|5.60 kWh/m²
+
|164.17 kWh/m²
 
|2000 Wh
 
|2000 Wh
|357
+
|12.18
 
|}
 
|}
 
*'''Month:''' The month of the year.
 
*'''Month:''' The month of the year.
 
*'''Average daily insolation:''' Solar resource data obtained for the location from [[Weather and solar resource data sources]].
 
*'''Average daily insolation:''' Solar resource data obtained for the location from [[Weather and solar resource data sources]].
 
*'''[[Load evaluation#Average daily watt-hours required|Average daily watt-hours required]]''' from load evaluation.
 
*'''[[Load evaluation#Average daily watt-hours required|Average daily watt-hours required]]''' from load evaluation.
*'''Ratio =''' Average daily watt-hours required ÷ Average daily insolation
+
*'''Ratio =''' Average daily watt-hours required ÷ Average monthly insolation
 +
 
 +
==Outputs==
 +
 
 +
{| class="wikitable" border=1 style="width: 80%;"
 +
! style="width: 20%"|Design daily insolation
 +
! style="text-align:left;"| = Average monthly insolation from month with the highest ratio ÷ 30
 +
|}
 +
 
 +
{| class="wikitable" border=1 style="width: 80%;"
 +
! style="width: 20%"|Design daily watt-hours required
 +
! style="text-align:left;"| = Average daily watt-hours from month with the highest ratio
 +
|}
  
 
==Notes/references==
 
==Notes/references==
 
<references/>
 
<references/>

Revision as of 10:53, 19 December 2020

The design process for an off-grid PV system should use conservative, worst-case values to ensure that the system is capable of meeting the energy needs of users throughout the year. There are many locations that have a significant seasonal variance in solar resource due to poor weather or latitude. Many off-grid PV systems will see a significant variance in how loads are used throughout the year, especially in locations that are only seasonally occupied. These two different factors - load usage vs. solar resource - make it important to determine what month to use in the system design as the worst-case scenario. An analysis of loads and usage could be performed on a monthly basis, but the most drastic shift in usage likely occurs between the major seasons in a given region meaning two to four times per year. Determining the worst-case month can be done using a simple table and a quick calculation. The values and calculation can be performed in Wh or kWh - the ratio is what is important. The two following values used for the design should be chosen from the month with the highest ratio of average daily watt-hours relative to average monthly insolation:

  • Design daily insolation
  • Design daily watt-hours required

Example 1: A potential off-grid PV system in Puerto Maldonado, Madre de Dios, Peru in the Amazon rainforest with PV source with a tilt of 12 degrees of PV module tilt. Solar resource data shows that despite being relatively near the equator there is significant monthly variation due to seasonal rains.[1] The load evaluation shows that loads will be used more frequently during the rainy season, which is common.

  • May (highlighted in red) has the worst ratio of solar resource relative to energy requirement throughout the year. The average monthly insolation value (135.47 kWh/m²) and Average daily Watt-hours required (3000Wh) from this month should be used in the design.
Month Average daily insolation Average daily watt-hours required Ratio
January 147.27 kWh/m² 2000 Wh 13.58
February 140.08 kWh/m² 2000 Wh 14.28
March 166.77 kWh/m² 2000 Wh 11.99
April 161.56 kWh/m² 3000 Wh 18.57
May 135.47 kWh/m² 3000 Wh 22.15
June 157.44 kWh/m² 3000 Wh 19.05
July 149.74 kWh/m² 3000 Wh 20.03
August 178.82 kWh/m² 3000 Wh 16.78
September 172.36 kWh/m² 3000 Wh 17.41
October 170.63 kWh/m² 2000 Wh 11.72
November 161.02 kWh/m² 2000 Wh 12.42
December 164.17 kWh/m² 2000 Wh 12.18

Outputs

Design daily insolation = Average monthly insolation from month with the highest ratio ÷ 30
Design daily watt-hours required = Average daily watt-hours from month with the highest ratio

Notes/references