[[File:Powrefactorgraphs.png|thumb|right|'''Top:''' A resistive load with a power factor of 1 (unity). Current, voltage and power are all in sync. '''Bottom:''' An inductive load with a power factor less than 1. Current is lagging (behind) the voltage phase. The yellow shaded area represents unconsumed power that is sent back to the source.]]
 
[[File:Powrefactorgraphs.png|thumb|right|'''Top:''' A resistive load with a power factor of 1 (unity). Current, voltage and power are all in sync. '''Bottom:''' An inductive load with a power factor less than 1. Current is lagging (behind) the voltage phase. The yellow shaded area represents unconsumed power that is sent back to the source.]]
 +
There are various [[Types of electricity#Alternating current|alternating current (AC)]] load types, some of which require voltage and current at the same time (resistive loads) and others that require voltage and current at different times (inductive and capacitive). Power factor (PF) is a number between -1 and 1 that can be applied to AC loads to describe to what degree their voltage and current demand (phases) are in sync. A load with a power factor of 1 (top graph at right) will have voltage and current peak simultaneously each cycle. A load with a power factor of less than 1 (bottom graph at right) will have voltage and current peak at different times each cycle.
 +
 +
The power factor of loads becomes important when sizing [[Inverter|off-grid inverters]]. A load with a power factor of less than 1 will require that the inverter supply current that exceeds the power rating of the appliance in order for it to work properly. This current is not included in the power rating of the appliance as it is not consumed by the load and is returned to the source. Power factor is therefore only factored into sizing the inverter, but is not relevant when sizing the [[PV module|PV source]] or [[Energy storage|energy storage system]].
 +
 +
==Calculating power factor==
 +
There are different types of power that are used to determine the power factor for a load.
 +
'''Power factor (PF) = real power / apparent power'''
 +
*Real power is power that is used to perform work. This power is consumed. Measured in Watts (W).
 +
*Reactive power is power that is power that does not perform work but is still present in a circuit. This power returns to the source. Measured in Volt-Amperes (VA).
 +
*Apparent power is the total power present in a circuit. Apparent power is the sum of real power and reactive power. Measured in Volt-Amperes (VA).
 +
 +
If the current and voltage of a circuit are measured for a circuit with a multimeter and multiplied this will be a measurement of apparent power. Devices specifically designed to measure power consumption, like a Kill-A-Watt meter, can measure real power.
 +
 +
==Examples of different load types==
 +
Common resistive loads are incandescent light bulbs or an electric heater. These loads will have a power factor of 1, which is also referred to as ‘’unity power factor.’’
 +
:'''Example 1:''' A 40W incandescent bulb is operating on a 120V AC circuit. You measure the current and get .3A. What is the power factor for this light bulb?
 +
:*Power factor  = 40W / (120V x .3A) = 1
 +
:*All power is consumed by the load.
 +
 +
Common inductive and capacitive loads are fans, televisions, radios, laptops, blenders, refrigerators, and LED lighting. These loads will have a power factor less than 1.
 +
:'''Example 2:''' A 20W laptop is operating on a 120V AC circuit. You measure the current and get .3A. What is the power factor for this laptop?
 +
:*Power factor  = 20W / (120V x .3A) = .5
 +
:*20W is consumed by the load the rest is reactive power that returns to the source.

Revision as of 10:05, 11 November 2020

Top: A resistive load with a power factor of 1 (unity). Current, voltage and power are all in sync. Bottom: An inductive load with a power factor less than 1. Current is lagging (behind) the voltage phase. The yellow shaded area represents unconsumed power that is sent back to the source.

There are various alternating current (AC) load types, some of which require voltage and current at the same time (resistive loads) and others that require voltage and current at different times (inductive and capacitive). Power factor (PF) is a number between -1 and 1 that can be applied to AC loads to describe to what degree their voltage and current demand (phases) are in sync. A load with a power factor of 1 (top graph at right) will have voltage and current peak simultaneously each cycle. A load with a power factor of less than 1 (bottom graph at right) will have voltage and current peak at different times each cycle.

The power factor of loads becomes important when sizing off-grid inverters. A load with a power factor of less than 1 will require that the inverter supply current that exceeds the power rating of the appliance in order for it to work properly. This current is not included in the power rating of the appliance as it is not consumed by the load and is returned to the source. Power factor is therefore only factored into sizing the inverter, but is not relevant when sizing the PV source or energy storage system.

Calculating power factor

There are different types of power that are used to determine the power factor for a load. Power factor (PF) = real power / apparent power

  • Real power is power that is used to perform work. This power is consumed. Measured in Watts (W).
  • Reactive power is power that is power that does not perform work but is still present in a circuit. This power returns to the source. Measured in Volt-Amperes (VA).
  • Apparent power is the total power present in a circuit. Apparent power is the sum of real power and reactive power. Measured in Volt-Amperes (VA).

If the current and voltage of a circuit are measured for a circuit with a multimeter and multiplied this will be a measurement of apparent power. Devices specifically designed to measure power consumption, like a Kill-A-Watt meter, can measure real power.

Examples of different load types

Common resistive loads are incandescent light bulbs or an electric heater. These loads will have a power factor of 1, which is also referred to as ‘’unity power factor.’’

Example 1: A 40W incandescent bulb is operating on a 120V AC circuit. You measure the current and get .3A. What is the power factor for this light bulb?
  • Power factor = 40W / (120V x .3A) = 1
  • All power is consumed by the load.

Common inductive and capacitive loads are fans, televisions, radios, laptops, blenders, refrigerators, and LED lighting. These loads will have a power factor less than 1.

Example 2: A 20W laptop is operating on a 120V AC circuit. You measure the current and get .3A. What is the power factor for this laptop?
  • Power factor = 20W / (120V x .3A) = .5
  • 20W is consumed by the load the rest is reactive power that returns to the source.