Example 1: A circuit has 3 x 12 AWG THHW wires. Can these wires fit in a 1/2" (21 mm) EMT conduit with 1 x 90° bend?
- Maximum fill of 40% of the space inside the conduit.
- Cross-sectional area of conduit: 195 mm²
- Cross-sectional area of 12 AWG THHN wire: 11.68 mm²