Difference between revisions of "Residual current device"

From Open Source Solar Project
Jump to navigation Jump to search
 
(21 intermediate revisions by the same user not shown)
Line 1: Line 1:
[[Category:Components]]
+
[[Category:Protection devices and disconnects]]
[[File:Rcd.png|250px|thumb|right|'''A diagram of a RCD in the output circuit of an inverter.'''<br/> 1. Is an integrated overcurrent protection device and residual current device. Both the ungrounded and grounded conductors pass through the RCD.]]
+
<languages />
A residual current device (RCD) or Ground Fault Circuit Interruptor (GFCI) is a device that constantly measures the current flowing between the outgoing and incoming wires of a circuit to see if there is a difference. If there is a difference, it means that there is a fault at some point in the circuit and a potential hazard. A RCD is typically incorporated into a [[Overcurrent protection|breaker]] or outlet so that it is able to disconnect the circuit upon identifying a difference in current or fault. RCDs are often required by the [[Electrical codes|electrical codes]] in many countries. In a [[Grounding system|grounded system]] this current is typically returning through the grounding system. RCDs are far more effective at preventing electrical accidents than OCPDs as they are far more sensitive and can therefore identify hazards more easily. All RCDs should include a test button (pictured in yellow in the diagram) that enables users to periodically make sure the device is functioning correctly.
+
<translate>
 +
<!--T:10-->
 +
[[File:Rcdlabeled.png|thumb|right|Wiring diagram of a stand-alone PV system with a charge controller with DC lighting control and an inverter for AC loads. ''(1)'' An integrated overcurrent protection device and residual current device is located on the inverter output. Both the ungrounded and grounded conductors pass through it.]]
  
A small amount of current - .1-.2 amps - can be sufficient for an electric shock to be lethal, yet the [[Overcurrent protection|overcurrent protection devices]] installed in electrical systems for lighting and outlets are generally 15 amps or more. Additionally, [[Overcurrent protection|overcurrent protection devices]] typically have a time delay to avoid accidentally opening (disconnecting) the circuit if there is a brief surge of current required by a [[Surge load|surge load]]. If there is insufficient current flowing to activate the [[Overcurrent protection|overcurrent protection device]], this can lead to a many faults and potential hazards going unnoticed until there is an accident. An RCD is far more sensitive - can be activated by as little as 5-30mA (.005-.03 A) of current - and will activate within 25-40ms (.025-.04 seconds). It is recommended that a RCD be incorporated into any system that has an [[Grounding system|grounding system]] on the alternating current (AC) side incorporate a RCD to improve the safety of an off-grid installation.
+
<!--T:11-->
 +
A residual current device (RCD) or Ground Fault Circuit Interruptor (GFCI) is a device that constantly measures the current flowing between the outgoing and incoming wires of a circuit to see if there is a difference. If there is a difference, it means that there is a fault at some point in the circuit and a potential hazard. A RCD is typically incorporated into a [[Special:MyLanguage/Overcurrent protection|breaker]] or outlet so that it is able to disconnect the circuit upon identifying a difference in current or fault. RCDs are often required by the [[Special:MyLanguage/Electrical codes|electrical codes]] in many countries. In a [[Special:MyLanguage/Grounding system|grounded system]] this current is typically returning through the grounding system. RCDs are far more effective at preventing electrical accidents than OCPDs as they are far more sensitive and can therefore identify hazards more easily. All RCDs should include a test button (pictured in yellow in the diagram) that enables users to periodically make sure the device is functioning correctly.
  
==Functioning of an RCD==
+
<!--T:12-->
An RCD works best relative to an OCPD in cases where there is a poor (high resistance) ground connection or no equipment ground for an appliance. In the example below a refrigerator is depicted with a loose/non-existant ground. There is a fault on L1 (ungrounded conductor) inside the refrigerator which is leaking some current to ground, but not enough to trigger an [[Overcurrent protection|overcurrent protection device]] or to cause it to stop working.  
+
A small amount of current - .1-.2 A - can be sufficient for an electric shock to be lethal, yet the [[Special:MyLanguage/Overcurrent protection device|overcurrent protection devices]] installed in electrical systems for lighting and outlets are generally 15 A or more. Additionally, [[Special:MyLanguage/Overcurrent protection device|overcurrent protection devices]] typically have a time delay to avoid accidentally opening (disconnecting) the circuit if there is a brief surge of current required by a [[Special:MyLanguage/Surge loads|surge load]]. If there is insufficient current flowing to activate the [[Special:MyLanguage/Overcurrent protection|overcurrent protection device]], this can lead to a many faults and potential hazards going unnoticed until there is an accident. An RCD is far more sensitive - can be activated by as little as 5-30 mA (.005-.03 A) of current - and will activate within 25-40 ms (.025-.04 seconds). It is recommended that an RCD is chosen with a 30 mA (.03 A) trip value.  
  
*'''Example 1:''' If the system does not have an RCD then the small amount of current flowing through ground will go undetected until a lower resistance path to ground is created, which in the example is created when a person touches the refrigerator. A larger amount of current now flows through the person to ground and may trigger [[Overcurrent protection|overcurrent protection device]] but not without electrocuting the person first.
+
<!--T:13-->
 +
It is recommended that a RCD be incorporated on the alternating current (AC) side of any off-grid system to improve its safety. RCDs can be found as [[Special:MyLanguage/Overcurrent protection device|breakers]] or integrated into outlets. RCDs can be put on individual circuits as a breaker or outlet or just one breaker can be used on the inverter output. RCDs on individual circuits increases system cost. One single RCD has the disadvantage of disconnecting all circuits if there is a fault, which can make it difficult to find the exact location of the fault during the [[Special:MyLanguage/Troubleshooting|troubleshooting process]].
 +
 
 +
==Functioning of an RCD== <!--T:14-->
 +
 
 +
<!--T:15-->
 +
An RCD works best relative to an OCPD in cases where there is a poor (high resistance) ground connection, or no equipment ground for an appliance. In the example below a refrigerator is depicted with a loose/non-existent ground. There is a fault on the ungrounded conductor (wire) inside the refrigerator, which is leaking some current to ground, but not enough to cause an [[Special:MyLanguage/Overcurrent protection|overcurrent protection device]] to [[Special:MyLanguage/Electricity and energy#Circuits|open]] (disconnect) the circuit or to cause the refrigerator to stop working.
 +
 
 +
<!--T:16-->
 +
'''Example 1:''' If the system does not have an RCD then the small amount of current flowing through ground will go undetected until a lower resistance path to ground is created, which in the example is created when a person touches the refrigerator. A larger amount of current now flows through the person to ground and may trigger [[Special:MyLanguage/Overcurrent protection|overcurrent protection device]] but not without electrocuting the person first.
 +
 
 +
<!--T:17-->
 
<gallery widths=250px>
 
<gallery widths=250px>
File:Wiithoutrcdexample.png|'''Example 1 - no RCD'''
+
File:Wiithoutrcdexample.png|Example 1 - no RCD
 
</gallery>
 
</gallery>
*'''Example 2:''' If the system has an RCD then the small amount of current flowing through ground will be quikcly detected and the fault/hazard will be mitigated by opening (disconnecting) the circuit. The refrigerator will stop functioning, but a person will be able to safely touch it without being electrocuted.
+
'''Example 2:''' If the system has an RCD then the small amount of current flowing through ground will be quickly detected and the fault/hazard will be mitigated by [[Special:MyLanguage/Electricity and energy#Circuits|opening]] (disconnecting) the circuit. The refrigerator will stop functioning, but a person will be able to safely touch it without being electrocuted.
 
<gallery widths=250px>
 
<gallery widths=250px>
File:Rcdexample.png|'''Example 2 - with RCD'''
+
File:Rcdexample.png|Example 2 - with RCD
 
</gallery>
 
</gallery>
 +
 +
==Notes/references== <!--T:18-->
 +
</translate>

Latest revision as of 06:40, 15 February 2021

Other languages:
English • ‎español
Wiring diagram of a stand-alone PV system with a charge controller with DC lighting control and an inverter for AC loads. (1) An integrated overcurrent protection device and residual current device is located on the inverter output. Both the ungrounded and grounded conductors pass through it.

A residual current device (RCD) or Ground Fault Circuit Interruptor (GFCI) is a device that constantly measures the current flowing between the outgoing and incoming wires of a circuit to see if there is a difference. If there is a difference, it means that there is a fault at some point in the circuit and a potential hazard. A RCD is typically incorporated into a breaker or outlet so that it is able to disconnect the circuit upon identifying a difference in current or fault. RCDs are often required by the electrical codes in many countries. In a grounded system this current is typically returning through the grounding system. RCDs are far more effective at preventing electrical accidents than OCPDs as they are far more sensitive and can therefore identify hazards more easily. All RCDs should include a test button (pictured in yellow in the diagram) that enables users to periodically make sure the device is functioning correctly.

A small amount of current - .1-.2 A - can be sufficient for an electric shock to be lethal, yet the overcurrent protection devices installed in electrical systems for lighting and outlets are generally 15 A or more. Additionally, overcurrent protection devices typically have a time delay to avoid accidentally opening (disconnecting) the circuit if there is a brief surge of current required by a surge load. If there is insufficient current flowing to activate the overcurrent protection device, this can lead to a many faults and potential hazards going unnoticed until there is an accident. An RCD is far more sensitive - can be activated by as little as 5-30 mA (.005-.03 A) of current - and will activate within 25-40 ms (.025-.04 seconds). It is recommended that an RCD is chosen with a 30 mA (.03 A) trip value.

It is recommended that a RCD be incorporated on the alternating current (AC) side of any off-grid system to improve its safety. RCDs can be found as breakers or integrated into outlets. RCDs can be put on individual circuits as a breaker or outlet or just one breaker can be used on the inverter output. RCDs on individual circuits increases system cost. One single RCD has the disadvantage of disconnecting all circuits if there is a fault, which can make it difficult to find the exact location of the fault during the troubleshooting process.

Functioning of an RCD

An RCD works best relative to an OCPD in cases where there is a poor (high resistance) ground connection, or no equipment ground for an appliance. In the example below a refrigerator is depicted with a loose/non-existent ground. There is a fault on the ungrounded conductor (wire) inside the refrigerator, which is leaking some current to ground, but not enough to cause an overcurrent protection device to open (disconnect) the circuit or to cause the refrigerator to stop working.

Example 1: If the system does not have an RCD then the small amount of current flowing through ground will go undetected until a lower resistance path to ground is created, which in the example is created when a person touches the refrigerator. A larger amount of current now flows through the person to ground and may trigger overcurrent protection device but not without electrocuting the person first.

Example 2: If the system has an RCD then the small amount of current flowing through ground will be quickly detected and the fault/hazard will be mitigated by opening (disconnecting) the circuit. The refrigerator will stop functioning, but a person will be able to safely touch it without being electrocuted.

Notes/references