Difference between revisions of "Charge controller programming"
Line 6: | Line 6: | ||
Charge controllers that allow programming will still often come with pre-programmed settings for different battery types and charging voltages, but it is recommended that all settings are examined and adjusted to the specifications of the specific system. | Charge controllers that allow programming will still often come with pre-programmed settings for different battery types and charging voltages, but it is recommended that all settings are examined and adjusted to the specifications of the specific system. | ||
*'''Nominal voltage:''' The nominal voltage of the battery bank. Typically 12V, 24V or 48V. | *'''Nominal voltage:''' The nominal voltage of the battery bank. Typically 12V, 24V or 48V. | ||
+ | *'''Battery type:'''Adjusts charging parameters for the particular type of battery. | ||
*'''Energy storage capacity:''' The total energy storage capacity of the system. This will be in Amp-hours (Ah) for [[Lead acid batteries|lead acid batteries]]. | *'''Energy storage capacity:''' The total energy storage capacity of the system. This will be in Amp-hours (Ah) for [[Lead acid batteries|lead acid batteries]]. | ||
+ | *'''[[Low voltage disconnect]]:''' If the charge controller has lighting control, this is the voltage at which any lighting will be turned off to protect the battery bank. Typically set at around 20% [[Energy storage#State of charge (SOC)|state of charge]]. | ||
*'''Charging set points:''' The voltages at which different charging phases start and stop vary depending on the battery type and manufacturer. Manufacturers of batteries will provide specific charging specifications in the product manual for bulk, absord, float, and equilization charging. These values will often be given as a range, it is recommended to program the charge controller to the upper end of the range for each of these values. | *'''Charging set points:''' The voltages at which different charging phases start and stop vary depending on the battery type and manufacturer. Manufacturers of batteries will provide specific charging specifications in the product manual for bulk, absord, float, and equilization charging. These values will often be given as a range, it is recommended to program the charge controller to the upper end of the range for each of these values. | ||
==Advanced settings== | ==Advanced settings== | ||
− | + | ===Maximum charge rate=== | |
− | The maximum amount of charging current that a type of battery can handle varies based upon its size, type and manufacturer. Specifications for the maxmimum charge rate can be found in the manual for the battery and will typically be given as a percentage of the [[Energy storage#Storage capacity|C-rate]]. [[Lead acid batteries#Flooded lead acid (FLA)|Flooded lead acid (FLA)]] batteries and [[Lead acid batteries#Valve-regulated lead acid (VRLA)|Gel]] batteries generally have a maximum charge rate | + | The maximum amount of charging current that a type of battery can handle varies based upon its size, type and manufacturer. Specifications for the maxmimum charge rate can be found in the manual for the battery and will typically be given as a percentage of the [[Energy storage#Storage capacity|C-rate]]. [[Lead acid batteries#Flooded lead acid (FLA)|Flooded lead acid (FLA)]] batteries and [[Lead acid batteries#Valve-regulated lead acid (VRLA)|Gel]] batteries generally have a maximum charge rate between 10%-20% of the C/20 rate.<ref name="rollsmanual"> Rolls Battery User Manual https://rollsbattery.com/public/docs/user_manual/Rolls_Battery_Manual.pdf</ref>. [[Lead acid batteries#Valve-regulated lead acid (VRLA)|Absorption glass mat (AGM)]] batteries are often able to accept higher charge currents, sometimes as high as 35% of their C/20 rate.<ref name="rollsmanual"/>.<br/> It is important that the maximum charge rate is set taking into account all parallel strings in the battery bank. |
− | + | :'''Example 1:''' A 48V system has 2 [[Series and parallel#Parallel connections|parallel]] strings of batteries rated at 205Ah @ C/20 rate. The recommended charge rate for this type of battery is 12% of the C/20 rate. What is the maximum charge rate for this battery bank? | |
− | + | ::Maximum charge rate = C/20 rate × parallel strings × manufacturer maximum C/20 rate percentage | |
− | + | ::Maximum charge rate = 205Ah x 2 parallel strings x .12 (12%) = 49.2A | |
− | + | ===Duration of absorption phase=== | |
The [[Charge controller#Charging phases|absorption phase]] of a charge controller holds the battery bank at a steady voltage for a set duration of time. A sufficiently long absorption phase is desirable as it ensures that the battery receives a full charge under substantial current, which is helpful to ensuring a long [[Energy storage#Cycle life|cycle life]]. The appropriate duration of an absorption charge depends upon the battery type, the size of the battery bank, and the maximum available charge rate for the system. A manufacturer may give a recommendation in the manual for the particular battery, although many do not. | The [[Charge controller#Charging phases|absorption phase]] of a charge controller holds the battery bank at a steady voltage for a set duration of time. A sufficiently long absorption phase is desirable as it ensures that the battery receives a full charge under substantial current, which is helpful to ensuring a long [[Energy storage#Cycle life|cycle life]]. The appropriate duration of an absorption charge depends upon the battery type, the size of the battery bank, and the maximum available charge rate for the system. A manufacturer may give a recommendation in the manual for the particular battery, although many do not. | ||
− | Rolls Battery recommends the following approaches for flooded lead acid (FLA) batteries:<ref name="rollsmanual"> Rolls Battery User Manual https://rollsbattery.com/public/docs/user_manual/Rolls_Battery_Manual.pdf</ref>.<br/> | + | Rolls Battery recommends the following approaches for flooded lead acid (FLA) batteries:<ref name="rollsmanual"> Rolls Battery User Manual https://rollsbattery.com/public/docs/user_manual/Rolls_Battery_Manual.pdf</ref><ref name="rollsFLAcharging"> Rolls FLA charging programming https://rollsbattery.com/public/docs/user_manual/Rolls_Battery_Manual.pdf</ref><br/> |
+ | |||
+ | |||
'''Absorption phase time = 0.42 × C ÷ I''' | '''Absorption phase time = 0.42 × C ÷ I''' | ||
*C = 20 hr rated capacity (total AH capacity of battery bank) | *C = 20 hr rated capacity (total AH capacity of battery bank) | ||
*I = Maximum available charging current provided by the [[PV source]]. This value can be calculated for different charge controller types as follows: | *I = Maximum available charging current provided by the [[PV source]]. This value can be calculated for different charge controller types as follows: | ||
::[[Charge controller#Charge controller types|PWM charge controller]] maximum available charge current = parallel strings × [[PV module#Module ratings|ISC]] | ::[[Charge controller#Charge controller types|PWM charge controller]] maximum available charge current = parallel strings × [[PV module#Module ratings|ISC]] | ||
− | ::[[Charge controller#Charge controller types|MPPT charge controller]] maximum available charge current = [[PV module#Module ratings| | + | ::[[Charge controller#Charge controller types|MPPT charge controller]] maximum available charge current = [[PV module#Module ratings|Total PV source power rating]] ÷ nominal system voltage |
:::This number may be limited by the programmed maximum charge rate for the charge controller or by the maximum output current of the charge controller, in which case that value should be used. | :::This number may be limited by the programmed maximum charge rate for the charge controller or by the maximum output current of the charge controller, in which case that value should be used. | ||
− | : | + | :'''Example 1:''' A battery bank has 2 strings of 6 Volt 6 CS 25P model batteries. These batteries are 853Ah each. The PV source has a maximum available charging current that is 10% of C/20 or 170Ah (2 parallel strings x 853Ah × .10 (10%) = 170Ah). |
− | + | :::Absorption phase time = 0.42 × (853Ah x 2 parallel strings) ÷ 170Ah | |
− | + | :::Absoprtion phase time = 4.2 hours | |
+ | |||
+ | Rolls Battery recommends the following approaches for flooded lead acid (FLA) batteries:<ref name="rollsmanual"> Rolls Battery User Manual https://rollsbattery.com/public/docs/user_manual/Rolls_Battery_Manual.pdf</ref><ref name="rollsFLAcharging"> Rolls FLA charging programming https://rollsbattery.com/public/docs/user_manual/Rolls_Battery_Manual.pdf</ref><br/> | ||
+ | |||
− | + | '''Absorption phase time = 0.42 × C ÷ I''' | |
− | + | *C = 20 hr rated capacity (total AH capacity of battery bank) | |
− | + | *I = Maximum available charging current provided by the [[PV source]]. This value can be calculated for different charge controller types as follows: | |
+ | ::[[Charge controller#Charge controller types|PWM charge controller]] maximum available charge current = parallel strings × [[PV module#Module ratings|ISC]] | ||
+ | ::[[Charge controller#Charge controller types|MPPT charge controller]] maximum available charge current = [[PV module#Module ratings|Total PV source power rating]] ÷ nominal system voltage | ||
+ | :::This number may be limited by the programmed maximum charge rate for the charge controller or by the maximum output current of the charge controller, in which case that value should be used. |
Revision as of 15:01, 4 November 2020
The simplest of charge controllers - rely upon factory settings and do not permit any programming. A charge controller is vital to ensuring the longevity or cycle life of batteries, therefore a charge controller that cannot be programmed must be carefully selected to ensure that the factory settings are appropriate for the type, voltage, and size of energy storage that will be used with the system. Charge controllers for all but the smallest systems offer varying degrees of programming from basic settings (system voltage, battery type) to complex modifications to how the charge controller regulates charging. With charge controllers that permit programming, it is necessary to have the manuals for the charge controller, battery type, and any communications systems on hand.
Contents
Basic settings
Charge controllers that allow programming will still often come with pre-programmed settings for different battery types and charging voltages, but it is recommended that all settings are examined and adjusted to the specifications of the specific system.
- Nominal voltage: The nominal voltage of the battery bank. Typically 12V, 24V or 48V.
- Battery type:Adjusts charging parameters for the particular type of battery.
- Energy storage capacity: The total energy storage capacity of the system. This will be in Amp-hours (Ah) for lead acid batteries.
- Low voltage disconnect: If the charge controller has lighting control, this is the voltage at which any lighting will be turned off to protect the battery bank. Typically set at around 20% state of charge.
- Charging set points: The voltages at which different charging phases start and stop vary depending on the battery type and manufacturer. Manufacturers of batteries will provide specific charging specifications in the product manual for bulk, absord, float, and equilization charging. These values will often be given as a range, it is recommended to program the charge controller to the upper end of the range for each of these values.
Advanced settings
Maximum charge rate
The maximum amount of charging current that a type of battery can handle varies based upon its size, type and manufacturer. Specifications for the maxmimum charge rate can be found in the manual for the battery and will typically be given as a percentage of the C-rate. Flooded lead acid (FLA) batteries and Gel batteries generally have a maximum charge rate between 10%-20% of the C/20 rate.[1]. Absorption glass mat (AGM) batteries are often able to accept higher charge currents, sometimes as high as 35% of their C/20 rate.[1].
It is important that the maximum charge rate is set taking into account all parallel strings in the battery bank.
- Example 1: A 48V system has 2 parallel strings of batteries rated at 205Ah @ C/20 rate. The recommended charge rate for this type of battery is 12% of the C/20 rate. What is the maximum charge rate for this battery bank?
- Maximum charge rate = C/20 rate × parallel strings × manufacturer maximum C/20 rate percentage
- Maximum charge rate = 205Ah x 2 parallel strings x .12 (12%) = 49.2A
Duration of absorption phase
The absorption phase of a charge controller holds the battery bank at a steady voltage for a set duration of time. A sufficiently long absorption phase is desirable as it ensures that the battery receives a full charge under substantial current, which is helpful to ensuring a long cycle life. The appropriate duration of an absorption charge depends upon the battery type, the size of the battery bank, and the maximum available charge rate for the system. A manufacturer may give a recommendation in the manual for the particular battery, although many do not.
Rolls Battery recommends the following approaches for flooded lead acid (FLA) batteries:[1][2]
Absorption phase time = 0.42 × C ÷ I
- C = 20 hr rated capacity (total AH capacity of battery bank)
- I = Maximum available charging current provided by the PV source. This value can be calculated for different charge controller types as follows:
- PWM charge controller maximum available charge current = parallel strings × ISC
- MPPT charge controller maximum available charge current = Total PV source power rating ÷ nominal system voltage
- This number may be limited by the programmed maximum charge rate for the charge controller or by the maximum output current of the charge controller, in which case that value should be used.
- Example 1: A battery bank has 2 strings of 6 Volt 6 CS 25P model batteries. These batteries are 853Ah each. The PV source has a maximum available charging current that is 10% of C/20 or 170Ah (2 parallel strings x 853Ah × .10 (10%) = 170Ah).
- Absorption phase time = 0.42 × (853Ah x 2 parallel strings) ÷ 170Ah
- Absoprtion phase time = 4.2 hours
Rolls Battery recommends the following approaches for flooded lead acid (FLA) batteries:[1][2]
Absorption phase time = 0.42 × C ÷ I
- C = 20 hr rated capacity (total AH capacity of battery bank)
- I = Maximum available charging current provided by the PV source. This value can be calculated for different charge controller types as follows:
- PWM charge controller maximum available charge current = parallel strings × ISC
- MPPT charge controller maximum available charge current = Total PV source power rating ÷ nominal system voltage
- This number may be limited by the programmed maximum charge rate for the charge controller or by the maximum output current of the charge controller, in which case that value should be used.
- This number may be limited by the programmed maximum charge rate for the charge controller or by the maximum output current of the charge controller, in which case that value should be used.