Wire terminal

From Open Source Solar Project
Revision as of 09:55, 27 October 2020 by Alex (talk | contribs) (Created page with "Category:Power distribution File:Terminals.png|thumb|right|'''Different terminal types:'''<br/>'''1.''' Uninsulated T16-8 terminal. Accepts 16mm² wire and has an M8 hol...")
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Different terminal types:
1. Uninsulated T16-8 terminal. Accepts 16mm² wire and has an M8 hole. 2. Insulated ring terminal. Accepts 4-6mm² wire and has an M6 hole.

Terminals are used to make safe and lasting mechanical connections in electrical systems. Terminals that are mechanically crimped with a tool are the standard for off-grid PV installations. A terminal must be properly chosen based upon:

  1. The size wire that wil be inserted into it. Terminals will often be marked for the size wire that they will except like in the diagram.
  2. The size bolt that will be used to anchor it. Terminals should be marked for the size hole that they have.
  3. The stranding of the wire that it will be used with. Fine stranded battery cable may require larger terminals for it to be properly secured.

When crimping the terminal, the proper size crimping tool must be used to ensure a good connection. If an improper tool is used, it is likely that the connection will come lose and fail over time.

Insulated terminals

Terminals for smaller wire gauges have been standardized using a simple color scheme that works for both AWG and mm² wire sizes.